8 S1 RELAY SETUP
8.5 EVENT RECORDER
8
8.5 EVENT RECORDER
8.5.1 DESCRIPTION
The relay captures a wide variety of events and stores the last 128 in non-volatile memory. See Section 6.5: A4
EVENT RECORDER on page 6–18 for details. A single power system disturbance could conceivably fill half of
the event recorder due to the various events that can be captured. Also, some events may happen on a regular
basis as part of a control scheme (e.g. Power Factor events in a capacitor bank switching scheme). For this
reason, certain event types can be ‘filtered’ from the event recorder to save room for other events. The follow-
ing setpoints describe the events that can be filtered.
8.5.2 SETTINGS
■
EVENT RECORDER
■
[ENTER] for more
The Event Recorder setpoints path is:
\ SETPOINTS \ S1 RELAY SETUP \ EVENT RECORDER
EVENT RECORDER
FUNCTION: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of all events. Disabling the
event recorder will not clear any data in the event recorder.
RECORD PICKUP
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of element pickup events.
RECORD DROPOUT
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of element dropout events.
RECORD TRIP
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of events that occur when
an element that has been programmed to the
Trip
or
Trip & AR
function oper-
ates.
RECORD ALARM
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of events that occur when
an element that has been programmed to the
Alarm
function operates.
RECORD CONTROL
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Enabled
for this setpoint to permit recording of events that occur when
an element that has been programmed to the
Control
function operates.
RECORD LOGIC INPUT
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of logic input events.
RECORD DATE/TIME
EVENTS: Enabled
Range: Enabled, Disabled
Enter
Disabled
for this setpoint to inhibit recording of set date and set time
events.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...