17-
52
750/760 Feeder Management Relay
GE Power Management
17.9 CONTROL SCHEMES
17 COMMISSIONING
17
If setpoint
OVERCURRENT P/U INHIBIT
is to be Enabled
1.
Assert logic input Setpoint Group 2. The faceplate LED should indicate the relay is using setpoint group 2.
2.
Inject current above the pickup setting of an overcurrent element that is not Disabled.
3.
De-assert logic input Setpoint Group 2. The LED on the faceplate should indicate the relay is still using set-
point group 2.
4.
Reduce the injected current until the overcurrent element resets.
5.
The LED on the faceplate should indicate the relay is now using setpoint group 1. Turn current off.
If setpoint
OVERVOLT P/U INHIBIT
is to be Enabled
1.
Assert logic input Setpoint Group 2. The faceplate LED should indicate the relay is using setpoint group 2.
2.
Inject voltage above the pickup setting of an overvoltage element that is not Disabled.
3.
De-assert logic input Setpoint Group 2. The LED on the faceplate should indicate the relay is still using set-
point group 2.
4.
Reduce the injected voltage until the overvoltage element resets.
5.
The LED on the faceplate should indicate the relay is now using setpoint group 1. Turn voltage off.
If setpoint
UNDERVOLT P/U INHIBIT
is to be Enabled
1.
Inject voltage above the pickup setting of an undervoltage element that is not Disabled.
2.
Assert logic input Setpoint Group 2. The faceplate LED should indicate the relay is using setpoint group 2.
3.
Reduce voltage below the pickup setting of an undervoltage element that is not Disabled.
4.
De-assert logic input Setpoint Group 2. The LED on the faceplate should indicate the relay is still using set-
point group 2.
5.
Increase the injected voltage until the undervoltage element resets.
6.
The LED on the faceplate should indicate the relay is now using setpoint group 1. Turn voltage off.
If setpoint
UNDERFREQ P/U INHIBIT
is to be Enabled
1.
Inject voltage with frequency above the pickup setting of an underfrequency element that is not Disabled.
2.
Assert logic input Setpoint Group 2. The faceplate LED should indicate the relay is using setpoint group 2.
3.
Reduce frequency below the pickup setting of an underfrequency element that is not Disabled.
4.
De-assert logic input Setpoint Group 2. The LED on the faceplate should indicate the relay is still using set-
point group 2.
5.
Increase the injected frequency until the underfrequency element resets.
6.
The LED on the faceplate should indicate the relay is now using setpoint group 1. Turn voltage off.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...