17 COMMISSIONING
17.9 CONTROL SCHEMES
17
3.
Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
4.
Reduce the injected voltages to cause an undervoltage trip, then set
V
bn
and
V
cn
to 0
5.
Slowly raise
V
an
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
an
.
6.
Repeat steps 3 through 5 except adjust
V
bn
and
V
cn
in turn.
Procedure To Check Minimum Voltage with Two Phases For Operation:
1.
Assert or De-assert a logic input to simulate an open breaker.
2.
Set Undervolt Restore Delay to 0.
3.
Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
4.
Reduce the injected voltages to cause an undervoltage trip, then set V
bn
to 0 and V
cn
to nominal.
5.
Slowly raise
V
an
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
an
with
V
cn
.
6.
Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
7.
Reduce the injected voltages to cause an undervoltage trip, then set
V
cn
to 0 and
V
bn
to nominal.
8.
Slowly raise
V
an
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
an
with
V
bn
.
9.
Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
10. Reduce the injected voltages to cause an undervoltage trip, then set
V
cn
to 0 and
V
an
to nominal.
11. Slowly raise
V
bn
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
bn
with V
an
.
12. Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
13. Reduce the injected voltages to cause an undervoltage trip, then set
V
an
to 0 and
V
cn
to nominal.
14. Slowly raise
V
bn
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
bn
with
V
cn
.
15. Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
16. Reduce the injected voltages to cause an undervoltage trip, then set
V
an
to 0 and
V
bn
to nominal.
17. Slowly raise
V
cn
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
cn
with
V
bn
.
18. Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
19. Reduce the injected voltages to cause an undervoltage trip, then set
V
bn
to 0 and
V
an
to nominal.
20. Slowly raise
V
cn
until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERVOLT
RESTORE MIN VOLTS
for
V
cn
with
V
an
.
Procedure To Check Minimum Voltage with Three Phases For Operation:
1.
Assert or De-assert a logic input to simulate an open breaker.
2.
Set Undervolt Restore Delay to 0.
3.
Inject
V
an
=
V
bn
=
V
cn
= nominal voltage into the bus voltage input of the relay.
4.
Reduce the injected voltages to cause an undervoltage trip, then set
V
an
and
V
cn
to nominal.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...