750/760 Feeder Management Relay
GE Power Management
16.3 MODBUS PROTOCOL
16 COMMUNICATIONS
16
16.3.8 FUNCTION CODE 06H - STORE SINGLE SETPOINT
This function code allows the master to modify the contents of a single setpoint register in a 750/760. Setpoint
registers are always 16 bit (two byte) values transmitted high order byte first. See Table 16–15: MODBUS
MEMORY MAP on page 16–18. The following table shows the format of the master and slave packets. It
shows a master device storing the value 200 at memory map address 1100h to slave device 11.
16.3.9 FUNCTION CODE 10H - STORE MULTIPLE SETPOINTS
This function code allows the master to modify the contents of a one or more consecutive setpoint registers in
a 750/760. Setpoint registers are 16 bit (two byte) values transmitted high order byte first. The maximum num-
ber of setpoint registers that can be stored in a single packet is 60. The table below shows the format of the
master and slave packets. It shows a master device storing the value 200 at memory map address 1100h, and
the value 1 at memory map address 1101h to slave device 11.
Table 16–6: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 06H
MASTER TRANSMISSION
SLAVE RESPONSE
PACKET FORMAT
EXAMPLE (HEX)
PACKET FORMAT
EXAMPLE (HEX)
SLAVE ADDRESS
11
SLAVE ADDRESS
11
FUNCTION
CODE 06
FUNCTION
CODE 06
DATA STARTING ADDRESS - hi
11
DATA STARTING ADDRESS - hi
11
DATA STARTING ADDRESS - lo
00
DATA STARTING ADDRESS - lo
00
DATA - hi
00
DATA - hi
00
DATA - lo
C8
DATA - lo
C8
CRC - lo
8F
CRC - lo
8F
CRC - hi
F0
CRC - hi
F0
Table 16–7: MASTER/SLAVE PACKET FORMAT FOR FUNCTION CODE 10H
MASTER TRANSMISSION
SLAVE RESPONSE
PACKET FORMAT
EXAMPLE (HEX)
PACKET FORMAT
EXAMPLE (HEX)
SLAVE ADDRESS
11
SLAVE ADDRESS
11
FUNCTION
CODE 10
FUNCTION
CODE 10
DATA STARTING ADDRESS - hi
11
DATA STARTING ADDRESS - hi
11
DATA STARTING ADDRESS - lo
00
DATA STARTING ADDRESS - lo
00
NUMBER OF SETPOINTS - hi
00
NUMBER OF SETPOINTS - hi
00
NUMBER OF SETPOINTS - lo
02
NUMBER OF SETPOINTS - lo
02
BYTE COUNT
04
CRC - lo
46
DATA #1 - high order byte
00
CRC - hi
64
DATA #1 - low order byte
C8
DATA #2 - high order byte
00
DATA #2 - low order byte
01
CRC - low order byte
27
CRC - high order byte
01
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...