16-
82
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
F82
TRACE MEMORY / DATA LOGGER TRIGGER
0x0001
Trigger on pickup
0x0002
Trigger on dropout
0x0004
Trigger on trip
0x0008
Trigger on alarm
0x0010
Trigger on control
F83
1
PHASE SEQUENCE
0
ABC
1
ACB
F84
1
OVERCURRENT DIRECTION
0
Disabled
1
Forward
2
Reverse
F85
1
PICKUP TYPE
0
Over
1
Under
F86
1
AUTO-RANGING POWER / ENERGY
All power quantities auto-range to display units relative to the nominal power of the system as
defined below. Multiply the power quantity in question by the multiplier in register 0316h to
yield the correct reading. The SI prefix for all power and energy quantities before scaling by
the multiplier is ‘k’. All power quantities are signed, single word registers (F4).
All energy quantities are unsigned, double word registers (F7).
The multiplier is determined from the nominal power which is defined as the product of three
setpoints: P
N
= Phase CT Primary x Bus VT Secondary Voltage x Bus VT Ratio
Example: If the 3
φ
Real Power register (0310) has a value of ‘123’ and the Multiplier register
(0316) has a value of ‘10’ then the value to display is 1230 kW.
F87
3
UNDERVOLTAGE RESTORATION SOURCE
0
Bus
1
Line
F88
6
RESERVED FOR MOD 010
0
1
Table 16–16: MODBUS MEMORY MAP DATA FORMATS (Sheet 23 of 24)
TYPE
VALUE / BIT
MASK
DESCRIPTION
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–83.
NOMINAL POWER P
N
MULTIPLIER
P
N
< 1 MVA
1
1 MVA
≤
P
N
< 10 MVA
10
10 MVA
≤
P
N
100
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...