GE Power Management
750/760 Feeder Management Relay
12-
23
12 S5 PROTECTION
12.4 GROUND OVERCURRENT
12
12.4 GROUND OVERCURRENT
12.4.1 DESCRIPTION
Separate protection is provided for ground time overcurrent and ground instantaneous overcurrent. These ele-
ments monitor the ground current input on terminals G10 and H10. Ground overcurrent elements can be
blocked individually or as a group by logic inputs. Ground overcurrent elements can be controlled by the
ground directional element allowing operation for faults in the permitted direction only.
12.4.2 GROUND TIME OVERCURRENT
The equivalent of a single ground time overcurrent relay, ANSI device 51G, is programmed in this subgroup.
■
GROUND TIME OC
■
[ENTER] for more
The Ground Time Overcurrent setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ GROUND CURRENT \ GROUND TIME OC
GROUND TIME OC
FUNCTION: Disabled
Range: Disabled, Trip, Trip & AR, Alarm, Latched Alarm, Control
Select the required function.
GROUND TIME OC
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
GROUND TIME OC
PICKUP: 1.00 x CT
Range: 0.05 to 20.00 in steps of 0.01 x CT
Select the current level required.
GROUND TIME OC
CURVE: Ext Inverse
Range: Ext Inverse, Very Inverse, Norm Inverse, ..., Flex Curve B
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
GROUND TIME OC
MULTIPLIER:
1.00
Range: 0.00 to 100.00 in steps of 0.01
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
GROUND TIME OC
RESET: Instantaneous
Range: Instantaneous, Linear
See description in Section 12.1: TIME OVERCURRENT CURVE CHARAC-
TERISTICS on page 12–1.
GROUND TIME OC
DIRECTION: Disabled
Range: Disabled, Forward, Reverse
Select the direction(s) of current flow for which operation is permitted.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...