750/760 Feeder Management Relay
GE Power Management
12.2 DIRECTIONAL OVERCURRENT CHARACTERISTICS
12 S5 PROTECTION
12
Figure 12–2: VOLTAGE RESTRAINT CHARACTERISTIC FOR PHASE-TIME OVERCURRENT
If voltage restraint is enabled, the adjusted pickup, calculated by adjusting the pickup value
by the multiplier, will not fall below 0.05
×
CT, which is the lowest setting for the PHASE TIME
OC PICKUP.