GE Power Management
750/760 Feeder Management Relay
12-
25
12 S5 PROTECTION
12.4 GROUND OVERCURRENT
12
12.4.3 GROUND INSTANTANEOUS OVERCURRENT
The equivalent of a single ground instantaneous relay, ANSI device 50G, is programmed in this subgroup.
■
GROUND INST OC
■
[ENTER] for more
The Ground Instantaneous Overcurrent setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ GROUND CURRENT \ GROUND INST OC
GROUND INST OC
FUNCTION: Disabled
Range: Disabled, Trip, Trip & AR, Alarm, Latched Alarm, Control
Select the required function.
GROUND INST OC
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
GROUND INST OC
PICKUP: 1.00 x CT
Range: 0.05 to 20.00 in steps of 0.01 x CT
Enter the pickup in terms of the CT rating. For example, if a pickup of 1000A is
required, enter
5.00 x CT
with a 200:5 ground CT installed.
GROUND INST OC
DELAY:
0.00 s
Range: 0.00 to 600.00 in steps of 0.01 s
Select the delay required.
GROUND INST OC
DIRECTION: Disabled
Range: Disabled, Forward, Reverse
Select the direction(s) of current flow for which operation is permitted.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...