17-
14
750/760 Feeder Management Relay
GE Power Management
17.6 METERING
17 COMMISSIONING
17
b) BUS VOLTAGE FREQUENCY
Expected Accuracy:
Frequency:
± 0.02 Hz of injected value within the range 16.00 to 90.00 Hz
Undervoltage Inhibit:
10 V secondary
Actual Values Displays:
Under subheading
A2 METERING \ FREQUENCY \
SYSTEM FREQUENCY
Procedure:
1.
Inject a voltage of nominal value at nominal frequency into phase A. Check that the frequency is measured
and displayed.
2.
Check the undervoltage inhibit level by slowly reducing the voltage until the frequency is no longer mea-
sured, and "0.00 Hz" is displayed.
3.
Return the voltage to nominal. Adjust the frequency above and below nominal, and note the frequency
measured by the relay.
Actual Values Displays:
Under subheading
A2 METERING \ FREQUENCY \
FREQUENCY DECAY RATE
Procedure:
Vary the frequency of the phase A voltage and verify the measured
FREQUENCY DECAY RATE
.
c) SYNCHRO VOLTAGE AND SYNCHRO FREQUENCY
Expected Accuracy:
Voltage:
± 0.68 V for 50 to 130 V
Frequency: ± 0.02 Hz of injected value within the range 16.00 to 90.00 Hz
Actual Values Displays:
Under subheading
A2 METERING \ SYNCHRO VOLTAGE \
SYNCHRO VOLTAGE
(Phasor)
SYNCHRO FREQUENCY
SYNCHRO DELTA
∆
F:
∆
V:
∆
F:
Procedure:
Inject voltage of various magnitudes and frequencies into the line voltage input and verify the displays.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...