16-
46
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
17CB
Reserved for MOD 008
0.0 to 6000.0
s
F2
10.0 s
S5
5
NEUTRAL DISPLACEMENT
READ/WRITE
17CE
Neutral Displacement Function
---
---
F39
Disabled
17CF
Neutral Displacement Relays
---
---
F57
None
17D0
Neutral Displacement Pickup
0.00 to 1.25
x VT
F3
1.00 x VT
17D1
Neutral Displacement Multiplier
0.00 to 100.00
---
F3
1.00
17D2
Neutral Displacement Curve
---
---
F36
Ext. Inverse
17D3
Neutral Displacement Reset Time
---
---
F68
Instantaneous
S6
PHASE CURRENT LEVEL
READ/WRITE
1800
Phase Current Level Function
---
---
F38
Disabled
1801
Phase Current Level Relays
---
---
F57
None
1802
Phase Current Level Pickup
0.05 to 20.00
x CT
F3
1.10 x CT
1803
Phase Current Level Delay
0 to 60,000
s
F1
2 s
S6
NEUTRAL CURRENT LEVEL
READ/WRITE
1808
Neutral Current Level Function
---
---
F38
Disabled
1809
Neutral Current Level Relays
---
---
F57
None
180A
Neutral Current Level Pickup
0.05 to 20.00
x CT
F3
1.10 x CT
180B
Neutral Current Level Delay
0 to 60,000
s
F1
2 s
S6
POWER FACTOR 1
READ/WRITE
1810
Power Factor 1 Function
---
---
F38
Disabled
1811
Power Factor 1 Relays
---
---
F57
None
1812
Power Factor 1 Pickup (+ Lag, - Lead)
-0.99 to +1.00
---
F6
0.80 Lag
1813
Power Factor 1 Dropout (+ Lag, - Lead)
-0.99 to +1.00
---
F6
1
1814
Power Factor 1 Delay
0 to 60,000
s
F1
50 s
S6
POWER FACTOR 2
READ/WRITE
1818
Power Factor 2 Function
---
---
F38
Disabled
1819
Power Factor 2 Relays
---
---
F57
None
181A
Power Factor 2 Pickup (+ Lag, - Lead)
-0.99 to +1.00
---
F6
0.80 Lag
181B
Power Factor 2 Dropout (+ Lag, - Lead)
-0.99 to +1.00
---
F6
1
181C
Power Factor 2 Delay
0 to 60,000
s
F1
50 s
S6
FAULT LOCATOR
READ/WRITE
1830
Length of Feeder
0.1 to 99.9
km, mi
F2
0.1
1831
Units of Length
---
---
F75
km
1832
Zpos (Resistive) of Feeder
0.01 to 99.99
Ω
F3
0.01
Ω
1833
Zpos (Inductive) of Feeder
0.01 to 99.99
Ω
F3
0.01
Ω
1834
Zzero (Resistive) of Feeder
0.01 to 99.99
Ω
F3
0.01
Ω
1835
Zzero (Inductive) of Feeder
0.01 to 99.99
Ω
F3
0.01
Ω
Table 16–15: MODBUS MEMORY MAP (Sheet 29 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...