GS8593-EX.3
GYB15.1676
CZ.GS8593-EX.Y.11(S)E-3.4/19.01
5
4
1
2
3
3
2
1
XK06-014-00557
Connections
(1) This
barrier
adopts
knock
-
down
connector
with
screw
terminals
.
The
intrinsically
safe
(
IS
for
short
)
terminals
(
blue
plugs
)
should
be
connected
to
hazardous
area
devices
and
the
non
-
IS
ones
(
green
plugs
)
to
the
safe
area
devices;
(2). Blue-marked wires should be chosen
for
hazardous
area, which
2
minimum
cross
section
area
should
be 0
.
5
mm
,
and
minimum
dielectric
strength
should
be
500V;
(3). Wiring
between
safe
area
and
hazardous
area
must
be
separated
,
and
both
have
protection
bushes;
(4). Wires with 8mm-long bared part should be fixed
by
M3
bolts
.
See
as
shown
below
.
.
Installation
The
isolated
barrier
should
be
located
i
n
safe
area
,
according
to
the
related
requirements in IEC60079-17(EN60079-17) and IEC60079-
19(EN60079-19)
.
GS8500-EX
series
isolated
barrier
are
designed
for
mounting
on
35mm
DIN
guide
rail
.
Install
with
the
following
steps
:
(
1
).
First,
lock
bus-powered
outlet
into
guide
rail;
(
If
no
bus
-
powered
function
,
skip
this
step
)
(
2
).
L
ock
the
upside
of
the
barrier
into
guide
rail;
(
3
).
Push
the
downside
of
the
barrier
into
rail
.
Disassembly
(
1
).
Insert
a
screwdriver
(
tip-size
≤
6mm
)
into
the
metal
lock
on
the
bottom
of
barrier;
(
2
).
Push
the
screwdriver
upwards
,
then
prize
the
metal
lock
downwards;
(
3
).
Take
the
barrier
out
of
guide
rail
.
(
1
).
Before using the barrier, please
check
again
whether Ex-proof rating
of module is in accord with operating conditions, and
wiring
and
polarity
are
correct;
(
2
).
It
is
unallowed
to
test
insulativity
among terminals
with
a
megameter
.
If
necessary
,
wires
must
be
cut
off
before
test
,
or
the
internal
fuse
will
blow;
(
3
).
Every
product
has
been
tested
strictly
before
leaving
factory
.
If
users
find
any
abnormality
in
the
module
,
please
contact
the
nearest
agent
or
our
company;
(
4
).
In
5
years
from
delivery
date
,
if
the
product
works
improperly
during
normal
operation
,
we
will
repair
or
replace
it
without
payment
.
Non
-
intrinsically safe terminals
Intrinsically safe terminals
Maintenance
Isolated Barrier
User
Manual
Caution
Please check whether the product type on package and label
is in accord with ordering contract;
Read this manual carefully before installation or use. If there is
something unclear, please dial technic support hotline-400 881 0780;
Isolated barrier should be located in safe area;
Supply voltage is 24VDC. 220VAC is forbidden;
Users are not allowed to dismantle or repair the barrier, otherwise
it will induce malfunction.
Please read user manual carefully before using the product, and please
keep it safe.
M3
8.0
YEAR
YEAR
WARRANTY
WARRANTY
Add: Building 6, 201 Minyi Road, Caohejing Hi-Tech Park
Songjiang New Industrial Park, Shanghai 201612, P.R. China
Tel : +86-21-64513350 Fax : +86-21-64846984
:
chenzhu
@
chenzhu
-
inst
.
com