![GE 750 Скачать руководство пользователя страница 197](http://html.mh-extra.com/html/ge/750/750_instruction-manual_131794197.webp)
GE Power Management
750/760 Feeder Management Relay
12-
45
12 S5 PROTECTION
12.6 NEGATIVE SEQUENCE
12
12.6.4 NEGATIVE SEQUENCE DIRECTIONAL
The negative sequence directional feature controls the operation of all negative sequence overcurrent ele-
ments and allows them to discriminate between forward or reverse faults. Refer to Section 12.2: DIREC-
TIONAL OVERCURRENT CHARACTERISTICS on page 12–6 for more details on directional principles. The
operating current and polarizing voltage is shown in the following table. If the polarizing voltage drops below
the ‘Minimum Operating Voltage’ setting the direction defaults to forward.
The setpoints for Negative Sequence Directional are as follows.
Table 12–12: NEGATIVE SEQUENCE DIRECTIONAL CHARACTERISTICS
QUANTITY
OPERATING CURRENT
POLARIZING VOLTAGE
Negative Sequence (ABC phase sequence)
Negative Sequence (ACB phase sequence)
■
NEG SEQ DIRECTION
■
[ENTER] for more
The Negative Sequence Directional setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ NEGATIVE SEQUENCE \ NEG SEQ DIRECTION
NEG SEQ DIRECTIONAL
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
Select the required function.
NEG SEQ DIRECTIONAL
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays to operate.
NEG SEQ DIRECTIONAL
MTA: 315° Lead
Range: 0 to 359 Lead in steps of 1
°
Enter the maximum torque angle by which the operating current leads the
polarizing voltage. This is the angle of maximum sensitivity.
MINIMUM POLARIZING
VOLTAGE: 0.05 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
As the system negative sequence voltage is used as the polarizing voltage for
this element, a minimum level of voltage must be selected to prevent operation
caused by system unbalanced voltages or VT ratio errors. For well-balanced
systems and 1% accuracy VTs, this setpoint can be as low as 2% of VT nomi-
nal voltage. For systems with high-resistance grounding or floating neutrals,
this setpoint can be as high as 20%. The default value of
0.05 x VT
is appropri-
ate for most solidly grounded systems.
I
a2
I
a
a
2
I
b
aI
c
+
+
3
-----------------------------------
=
V
–
a2
V
a
a
2
V
b
aV
c
+
+
3
------------------------------------------
–
=
I
a2
I
a
aI
b
a
2
I
c
+
+
3
-----------------------------------
=
V
–
a2
V
a
aV
b
a
2
V
c
+
+
3
------------------------------------------
–
=
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...