2.1.1 DESCRIPTION
The relay has five types of display messages: actual value, setpoint, diagnostic, flash, and help. Actual values
are values that are measured by the relay such as current and voltage. Setpoints are programmable settings
entered by the user. These types of messages are located within a menu structure that groups the information
into categories. Navigating the menu structure is described below. A summary of the menu structure for actual
values and setpoints can be found in Sections 6.1: OVERVIEW on page 6–1 and 7.1: OVERVIEW on page 7–
1, respectively.
n
ACTUAL VALUES
n
A1 STATUS
Press the
key to display the header for the first actual values page.
The actual values pages are numbered, have an 'A' prefix for easy identifica-
tion and have a name which gives a general idea of the information available
in that page. Repeatedly pressing the
key will scroll through all the
available actual values page headers.
n
SETPOINTS
n
S1 RELAY SETUP
Press the
key to display the header for the first setpoints page. The
setpoint pages are numbered, have an 'S' prefix for easy identification and
have a name which gives a general idea of the settings available in that
page. Repeatedly pressing the
key will scroll through all the available
setpoint page headers.
n
CURRENT
n
[ENTER] for more
Press the
key until the page
A2 METERING
appears. Now press the
key and the first sub-page heading for page 2 of actual values
appears. Pressing the
and
keys will scroll the display up
and down through the sub-page headers.
n
DEMAND
n
[ENTER] for more
Press the
key until the
DEMAND
sub-page heading appears. Press
to display the messages in this sub-page.
n
PHASE A CURRENT
n
[ENTER] for more
Note that all heading messages have the
n
symbol preceding them and that
only some sub-pages have a subsequent second sub-page.
LAST PHASE A CURRENT
DEMAND: 0
A
Press the
key to display the actual values of this second sub-page.
Actual values messages and setpoints always have a colon separating the
name of the value and the actual value or setpoint. This particular message
displays the last phase A current demand as measured by the relay. The
menu path to this particular message is referred to as
A2 METERING \ DEMAND
\ PHASE A CURRENT \ LAST PHASE A CURRENT DEMAND
. Messages are referred
to in this manner throughout the manual.
MAX PHASE A CURRENT
DEMAND: 0
A
Press the
key and the next actual value display message will
appear. Pressing the
and
keys will scroll the display up
and down through all the actual value displays in this second sub-page.
n
PHASE A CURRENT
n
[ENTER] for more
Pressing the
key reverses the process described above and returns
the display to the previous level. Press the
key twice to return to the
A2 METERING \ DEMAND
sub-page header.
A C T U A L
A C T U A L
A C T U A L
E N T E R
E N T E R
E S C A P E
E S C A P E
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...