17-
64
750/760 Feeder Management Relay
GE Power Management
17.9 CONTROL SCHEMES
17 COMMISSIONING
17
c) PROCEDURE TO CHECK MINIMUM FREQUENCY
1.
Assert or De-assert a logic input to simulate an open breaker.
2.
Set
UNDERFREQ RESTORE DELAY
to
0
.
3.
Inject nominal voltage into the bus voltage input of the relay.
4.
Reduce the injected frequency to cause an underfrequency trip.
5.
Slowly increase the frequency until the 2 CLOSE relay operates. This is the operating level of setpoint
UNDERFREQ RESTORE MIN FREQ
.
17.9.7 TRANSFER SCHEME
a) COMMON LOGIC
1.
Ensure that the
PHASE INST O/C 1
,
NEUTRAL INST O/C 1
,
LINE UNDERVOLTAGE 3
,
LINE UNDERVOLTAGE 4
,
SYNCH-
ROCHECK
and
LOGIC INPUT
features in the relays programmed as Incomer 1 and Incomer 2 have been
tested and are
Enabled
.
2.
Ensure that the
SYNCHROCHECK
and
LOGIC INPUT
features in the relay programmed as Bus Tie has been
tested and is
Enabled
.
3.
Ensure all circuit breakers are disconnected from their normal positions in the primary circuit, are open and
operating properly, and the close and trip circuits have been tested and are energized.
4.
De-assert logic inputs 1, 2, 3, 4, 5, 6, 11, 12 and 13 at both Incomer relays. De-assert logic inputs 1, 2, 3,
4, 5, 6 and 11 at the Bus Tie relay.
5.
At this time both of the Incomer relays should have output relays 1 TRIP and 4 operated, output relays 5
through 7 reset, and be displaying the message Transfer Not Ready. At the Bus Tie breaker relay output
relays 4 through 7 should be reset (de-energized).
6.
Parallel the Line to Bus voltage inputs of the Incomer 1 relay to the Bus voltage input of the Bus Tie relay
and connect this circuit to a voltage source (Source 1 for these tests.) Do not energize the source.
7.
Parallel the Line to Bus voltage inputs of the Incomer 2 relay to the Line voltage input of the Bus Tie relay
and connect this circuit to a voltage source (Source 2 for these tests.) Do not energize the source.
8.
Assert logic input 5 (Breaker Connected) at the Bus Tie relay - output relays 4 and 6 on the Bus Tie relay
should operate.
9.
Assert logic input 5 (Breaker Connected) at the Incomer 1 relay - nothing should happen.
10. Assert logic input 2 (Remote Close) at the Incomer 1 relay - nothing should happen. Energize Source 1 at
nominal voltage - the Incomer 1 breaker should close, output relay 4 should reset and relays 5 and 7 on
the Incomer 1 relay should operate.
11. Assert logic input 5 (Breaker Connected) at the Incomer 2 relay - nothing should happen.
12. Assert logic input 2 (Remote Close) at the Incomer 2 relay - nothing should happen. Energize Source 2 at
nominal voltage - the Incomer 2 breaker should close, output relay 4 should reset and relays 5 and 7 on
the Incomer 2 relay should operate.
13. De-assert logic input 5 (Breaker Connected) at the Bus Tie relay - output relays 4 and 6 on the Bus Tie
relay should reset, and at both Incomer relays the message Transfer Not Ready should be displayed.
14. Assert logic input 5 (Breaker Connected) at the Bus Tie relay - output relays 4 and 6 on the Bus Tie relay
should operate, and at both Incomer relays the message Transfer Not Ready should be removed from the
display.
15. De-assert logic input 5 (Breaker Connected) at the Incomer 1 relay - at the Incomer 1 relay output relays 5
and 7 should reset; at both Incomer relays the message Transfer Not Ready should be displayed.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...