17-
60
750/760 Feeder Management Relay
GE Power Management
17.9 CONTROL SCHEMES
17 COMMISSIONING
17
17.9.5 UNDERVOLTAGE RESTORATION
Procedure To Check Logic and Timers
1.
Make connections per Figure 17–1: RELAY TEST WIRING – WYE CONNECTION or Figure 17–2: RELAY
TEST WIRING – DELTA CONNECTION on page 17–4.
2.
Note that Undervoltage 1 must be programmed, with the function as Trip, and Undervoltage 2 must be Dis-
abled.
3.
Assert or De-assert a logic input to simulate a closed breaker.
4.
Inject a balanced three-phase voltage at nominal voltage and frequency into the bus voltage input.
5.
Initially set the undervoltage restoration function setpoint to Alarm, and other setpoints as required.
6.
Turn the voltage off. After the programmed delay Undervoltage 1 should cause a trip, which should not ini-
tiate undervoltage restoration as the breaker is closed. Diagnostic message "Uvolt Restore Init" should not
be displayed.
7.
Assert or De-assert a logic input to simulate an open breaker, which should initiate undervoltage restora-
tion. The diagnostic alarm message and LED should be displayed, and any output relays programmed to
operate for this condition should operate.
8.
Change the Undervoltage Restoration function setpoint to Control, and the diagnostic message should
change to control and the ALARM LED should turn off. Return this setpoint to Alarm.
9.
Assert logic input Block Restoration. The diagnostic alarm message and LED should be removed from the
display, and any output relays that operated should reset.
10. De-assert the logic input. The alarm message and LED should again be displayed and output relays oper-
ated. After the delay programmed in Incomplete Sequence Time the alarm message and LED should be
removed from the display and output relays reset.
11. Return the reduced voltage to nominal, resetting both the undervoltage trip condition and undervoltage
restoration.
12. Reduce voltage until Undervoltage 1 trips, then immediately return the voltage to nominal. The diagnostic
alarm message and LED should be displayed, and output relays operated.
13. Provide a Reset to the relay, and the alarm message and LED should be removed from the display and
output relays reset. Remove the Reset.
14. Arrange the interval timer to start on appearance of voltage and stop when the 2 CLOSE relay operates.
15. Turn the voltage off to cause an Undervoltage 1 trip, then reset the timer.
16. Turn the voltage on. The 2 CLOSE relay should operate after the delay programmed in setpoint
UNDER-
VOLT RESTORE DELAY
.
17. If Undervoltage 2 initiation is to be checked change the
UNDERVOLTAGE RESTORATION
function setpoint to
Disabled
,
UNDERVOLTAGE 1 FUNCTION
to
Disabled
,
UNDERVOLTAGE 2 FUNCTION
to
Trip
and repeat steps 3
through 7.
a) FOR WYE VTs
Test Connections per Figure 17–1: RELAY TEST WIRING – WYE CONNECTION on page 17–4.
Procedure To Check Minimum Voltage with One Phase For Operation
1.
Assert or De-assert a logic input to simulate an open breaker.
2.
Set Undervolt Restore Delay to 0.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...