15-
6
750/760 Feeder Management Relay
GE Power Management
15.4 SIMULATION
15 S8 TESTING
15
The relay remains in the
Postfault State
until either a close command is sent to the relay, or the 760 autore-
close scheme has all requirements met and is ready to close. At this time the relay returns to the
Prefault
State
. Note that the 2 CLOSE relay is not allowed to operate. Setting the
SIMULATION STATE
setpoint to
Dis-
abled
also terminates simulation.
2.
If simulation of the feeder breaker is not required set the
CIRCUIT BREAKER SIMULATION
setpoint to
Disabled
.
After the required simulation setpoints have been entered, the relay is placed in simulation mode by setting
the
SIMULATION STATE
setpoint to
Prefault
. The relay replaces the normal AC inputs with those programmed
on the
PREFAULT VALUES
setpoint page. All logic inputs are monitored normally throughout the simulation
including any set to monitor the 52a/52b contacts by which the front panel Breaker Open and Breaker
Closed indicators are set.
Operation is similar to that described in (1) above except that the 1 TRIP relay will operate if a trip condition
is declared and the 2 CLOSE relay will operate in response to any form of close request. As well, the Sim-
ulation State is controlled by the monitored state of the breaker.
15.4.2 SETUP
■
SETUP
■
[ENTER] for more
The
SIMULATION SETUP
setpoints path is:
\ SETPOINTS \ S8 TESTING \ SIMULATION \ SETUP
SIMULATION STATE:
Disabled
Range: Disabled, Prefault, Fault, Postfault
This setpoint must be programmed to
Disabled
if actual system inputs are to
be monitored. If programmed to any other setting, the relay is in simulation
mode and actual system parameters are not monitored.
The system parameters simulated by the relay will be those in the section
below that corresponds to the programmed value of this setpoint. For example,
if programmed to
Fault
, then the system parameters will be set to those
defined by the setpoints in Section 15.4.4 FAULT VALUES on page 15–7.
Note: The simulation state may change due to a change in the operational
state of the relay. For example, if set to
Fault
and a trip opens the breaker
(either simulated or actual), the simulation state and this setpoint will automati-
cally change to
Postfault
.
CIRCUIT BREAKER
SIMULATION: Enabled
Range: Enabled, Disabled
An operator can use the simulation feature to provide a complete functional
test of the relay’s protection features, except for the measurement of external
input values. As this feature may be used for on-site testing, provision is made
to block the operation of the output relays so the operation of other equipment
is prevented. Enter
Enabled
to block the 1 TRIP and 2 CLOSE relays from
operating, and ignore the 52a/52b auxiliary contacts, even if installed. In this
mode, the circuit breaker will be simulated. Enter
Disabled
to allow the 1 TRIP
and 2 CLOSE relays to open and close an actual circuit breaker connected to
the relay. In this mode, the 52a/52b auxiliary contacts, if installed, will be read
for feedback from the breaker.
ALLOW OPERATION OF
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Relays 1 TRIP and 2 CLOSE are allowed to operate by entering
Disabled
for
CIRCUIT BREAKER SIMULATION
. Relays 3-7 AUXILIARY can also be allowed to
operate if selected by this setpoint. The 8 SELF-TEST WARNING relay is
always allowed to operate. Note that the default setting blocks the operation of
all output relays. For timing tests, a selected output relay can be set to be
operational, to provide a signal to stop a timer.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...