2
Underfrequency 1 Minimum Operating Voltage
0.00 to 1.25
x VT
F3
0.70 x VT
17A5
1
Underfrequency 1 Minimum Operating Current
0.00 to 20.00
x CT
F3
0.20 x CT
S5
UNDERFREQUENCY 2
READ/WRITE
17A8
Underfrequency 2 Function
---
---
F39
Disabled
17A9
Underfrequency 2 Relays
---
---
F57
None
17AA
Underfrequency 2 Pickup
20.00 to 65.00
Hz
F3
58.00 Hz
17AB
Underfrequency 2 Delay
0.00 to 600.00
s
F3
3.00 s
17AC
2
Underfrequency 2 Minimum Operating Voltage
0.00 to 1.25
x VT
F3
0.70 x VT
17AD
1
Underfrequency 2 Minimum Operating Current
0.00 to 20.00
x CT
F3
0.20 x CT
S5
LINE UNDERVOLTAGE 3
READ/WRITE
17B0
Line Undervoltage 3 Function
---
---
F39
Disabled
17B1
Line Undervoltage 3 Relays
---
---
F57
None
17B2
2
Line Undervoltage 3 Pickup
0.00 to 1.25
x VT
F3
0.75 x VT
17B3
Line Undervoltage 3 Delay
0.0 to 6000.0
s
F2
2.0 s
17B4
2
Line Undervoltage 3 Minimum Operating Voltage
0.00 to 1.25
x VT
F3
0.30 x V
17B5
Line Undervoltage 3 Curve
---
---
F45
Definite Time
S5
LINE UNDERVOLTAGE 4
READ/WRITE
17B8
Line Undervoltage 4 Function
---
---
F39
Disabled
17B9
Line Undervoltage 4 Relays
---
---
F57
None
17BA
2
Line Undervoltage 4 Pickup
0.00 to 1.25
x VT
F3
0.75 x VT
17BB
Line Undervoltage 4 Delay
0.0 to 6000.0
s
F2
2.0 s
17BC
2
Line Undervoltage 4 Minimum Operating Voltage
0.00 to 1.25
x VT
F3
0.30 x V
17BD
Line Undervoltage 4 Curve
---
---
F45
Definite Time
S5
FREQUENCY DECAY
READ/WRITE
17C0
1
Frequency Decay Function
---
---
F39
Disabled
17C1
1
Frequency Decay Relays
---
---
F57
None
17C2
1
Frequency Decay Rate
0.1 to 5.0
Hz/s
F2
1.0 Hz/s
17C3
1
Frequency Decay Pickup
20.00 to 65.00
Hz
F3
59.50 Hz
17C4
1
Frequency Decay Delay
0.00 to 600.00
s
F3
2.00 s
17C5
1
Frequency Decay Minimum Operating Voltage
0.00 to 1.25
x VT
F3
0.70 x VT
17C6
1
Frequency Decay Minimum Operating Current
0.00 to 20.00
x CT
F3
0.00 x CT
S5
5
RESERVED FOR MOD 008
READ/WRITE
17C8
Reserved for MOD 008
---
---
F39
Disabled
17C9
Reserved for MOD 008
---
---
F57
None
17CA
Reserved for MOD 008
0.015 to 0.600
x RATED
F70
0.050 x RATED
Table 16–15: MODBUS MEMORY MAP (Sheet 28 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...