750/760 Feeder Management Relay
GE Power Management
4.4 USING 750/760 PC
4 750/760 PC PROGRAM
4
5.
The 750/760 PC Program will automatically list file names ending with *.000 Click on the appropriate file
name such that it appears in the File Name box. Click on OK to continue.
6.
A similar dialog box as in step 3 will appear asking for the control board firmware file. Locate this file and
click on OK to continue.
7.
Another warning message will appear to ensure you want to continue. Click on the Yes button to continue.
8.
Upon completion, the program will put the relay back to “normal mode”.
9.
The setpoint file saved in step 1 can now be loaded into the relay. (see Section 4.4.6: LOADING SET-
POINTS FROM A FILE on page 4–10).
4.4.3 ENTERING SETPOINTS
The following example illustrates entering setpoints for
S2 SYSTEM SETUP / POWER SYSTEM
using the 750/760 PC
Program.
1.
From the Setpoint menu select System Setup
2.
From the System Setup window select the Sensing tab.
Figure 4–8: S2 SETPOINTS ENTRY DIALOG BOX
•
For setpoints requiring numerical values (i.e. Nominal Frequency) click the mouse anywhere inside the
setpoint box. This displays a numerical keypad showing the OLD value, RANGE and INCREMENT of
the setpoint being modified. The up/down arrows can also be used to increment/decrement the value.
•
For setpoints requiring non-numerical values (i.e. Phase Sequence) clicking anywhere inside the set-
point box or using the down arrow will cause a selection menu to be displayed.
3.
Click on OK when done. You will be prompted to store the setpoints.
•
Click on Cancel
to retain the previous value.
•
Click on Store to send the values to the 750/760 (if connected)
•
Click on Help to display help related to setpoints seen in this window
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...