4.4.7 USER MAP
The 750/760 PC Program provides a means to program the 750/760 User Map (MODBUS addresses 0x0180
to 01F7). Refer to section 16.4: MODBUS MEMORY MAP on page 16–18 for more information.
Selecting Setpoint > User Map opens the window below. This window allows the desired addresses to be writ-
ten to User Map locations. The User Map values that correspond to these addresses are then displayed.
Figure 4–12: USER MAP VALUES WINDOW
4.4.8 WAVEFORM CAPTURE (TRACE MEMORY)
The 750/760 PC Program can be used to view Waveform Capture or Trace Memory data stored by the relay.
Data is captured for analog current and voltage inputs (
Ia
,
Ib
,
Ic
,
Ig
,
Isg
,
Va
,
Vb
,
Vc
,
Vs
) as well as digital data
for the output relays and the contact inputs states.
To use the Waveform Capture function, run the 750/760 PC Program and establish communications with a
connected 750/760 relay.
Select Actual > Waveform Capture from the main window to open the Waveform Capture window. The win-
dow shown below will appear, showing the Phase A current of the last captured waveform. The red vertical line
shows the trigger point of the waveform.
The cursors (shown by a solid and dotted green line) can be moved to different points on the waveform to see
magnitude and delta time information. Waveform data can be saved to a CSV (Comma delimited) file by press-
ing the Save button. The Open button can open waveform data that has been stored to a CSV file.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...