10-
12
750/760 Feeder Management Relay
GE Power Management
10.9 AUTORECLOSE FUNCTIONS (760 ONLY)
10 S3 LOGIC INPUTS
10
10.9 AUTORECLOSE FUNCTIONS (760 ONLY)
10.9.1 DESCRIPTION
The following logic input functions are used in the autoreclose scheme. Refer to Section 14.8: AUTORE-
CLOSE (760 ONLY) on page 14–30 for more detail.
10.9.2 SETTINGS
■
RECLOSE FUNCTIONS
■
[ENTER] for more
The Autoreclose Functions setpoints path is:
\ SETPOINTS \ S3 LOGIC INPUTS \ RECLOSE FUNCTIONS
INITIATE RECLOSURE:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Initiates an autoreclose sequence leading to an operation of the 2 CLOSE
relay. This input will NOT cause the 1 TRIP output relay of the 760 to operate.
It is intended for use where the initiating device sends an independent trip to
the breaker at the same time it sends an initiate reclosure to the 760.
CANCEL RECLOSURE:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Cancels a reclosure sequence in progress and blocks the autoreclose scheme
from operating.
BLOCK RECLOSURE:
Disabled
Range: Disabled, Input 1, Input 2, ..., Input 20
Cancels a reclosure sequence in progress and blocks the autoreclose scheme
from operating.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...