GE Power Management
750/760 Feeder Management Relay
1-
11
1 PRODUCT OVERVIEW
1.2 TECHNICAL SPECIFICATIONS
1
1.2.5 MONITORING ELEMENTS
PHASE / NEUTRAL CURRENT
Pickup Level:
0.05 to 20.00 in steps of 0.01 x CT
Dropout Level:
97 to 98% of Pickup
Time Delay:
0 to 60000 in steps of 1 s (definite
time)
Level Accuracy:
Per current input
Timing Accuracy:
± 100 ms
POWER FACTOR 1 / 2
Required Voltage:
> 30% of nominal in all phases
Pickup Level:
0.50 Lag to 0.50 Lead in steps of
0.01
Dropout Level:
0.50 Lag to 0.50 Lead in steps of
0.01
Time Delay:
0 to 60 000 in steps of 1 s (definite
time)
Level Accuracy:
± 0.02
Timing Accuracy:
± 100 ms
ANALOG IN THRESHOLD 1 / 2
Pickup Level:
0 to 65535 in steps of 1 unit
Dropout Level:
Programmable from 2 to 20% of
Pickup (under or over)
Time Delay:
0 to 60000 in steps of 1 s
Level Accuracy:
± 1%
Timing Accuracy:
± 100 ms
ANALOG IN RATE 1 / 2
Pickup Level:
–1000 to 1000
µ
A/hr. in steps of 0.1
Dropout Level:
97 to 98% of Pickup
Time Delay:
0 to 60000.0 in steps of 1 s
Level Accuracy:
± 1%
Timing Accuracy:
± 100 ms
OVERFREQUENCY
Required Voltage:
> 30% of nominal in phase A
Pickup Level:
20.01 to 65.00 in steps of 0.01 Hz
Dropout Level:
Pickup - 0.03 Hz
Time Delay:
0.0 to 6000.0 in steps of 0.1 s
Level Accuracy:
± 0.02 Hz
Timing Accuracy:
at 60 Hz: ± 34 ms
at 50 Hz: ± 40 ms
FAULT LOCATOR
Range:
–327.68 to 327.66 km/miles
0 to 65534 Ohms
Memory:
stores the 10 most recent faults
DEMAND
(accuracies based on less than 2 x CT and 50 to 130 V
inputs)
Measured Values:
Phase A/B/C Current (A)
3
Φ
Real Power (MW)
3
Φ
Reactive Power (Mvar)
3
Φ
Apparent Power (MVA)
Measurement Type:
Thermal Exponential, 90%
response time (programmed): 5, 10,
15, 20, 30, or 60 min.
Block Interval / Rolling Demand,
time interval (programmed): 5, 10,
15, 20, 30, or 60 min.
Block Interval with Start Demand
Interval Logic Input pulses
A Pickup Level:
10 to 10000 in steps of 1
MW Pickup Level:
0.1 to 3000.0 in steps of 0.1
Mvar Pickup Level:
0.1 to 3000.0 in steps of 0.1
MVA Pickup Level:
0.1 to 3000.0 in steps of 0.1
Level Accuracy:
± 2%
VT FAILURE
Programmable to inhibit dependent features.
BREAKER FAILURE TO OPERATE
Time Delay:
30 to 1000 ms in steps of 10
Timing Accuracy:
0 to +20 ms error
ACCUMULATED ARCING CURRENT
Pickup Level:
1 to 50 000 kA
2
-seconds in steps of
1
Start Delay:
0 to 100 ms in steps of 1
TRIP / CLOSE COIL MONITORS
Detect open trip and close circuits.
PULSE OUTPUT
Pulse output is 1 second on time and one second off time
after the programmed interval.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...