16-
54
750/760 Feeder Management Relay
GE Power Management
16.4 MODBUS MEMORY MAP
16 COMMUNICATIONS
16
1B64
Undervoltage Restoration Delay
0 to 10000
s
F1
10 s
1B65
U nde rvo ltag e R esto ration Inco m p lete S e que nce Tim e
1 to 10,000
min.
F1
100 min.
1B66
3
Undervoltage Restoration Source
---
---
F87
Bus
S7
UNDERFREQUENCY RESTORATION
READ/WRITE
1B70
Underfrequency Restoration Function
---
---
F38
Disabled
1B71
Underfrequency Restoration Relays
---
---
F57
None
1B72
2
Underfrequency Restoration Minimum Voltage
0.00 to 1.25
x VT
F3
0.90 x V
1B73
8
Underfrequency Restoration Minimum Frequency
20.00 to 65.00
Hz
F3
59.90 Hz
1B74
Underfrequency Restoration Delay
0 to 10000
s
F1
10 s
1B75
U nderfrequency R estoration Incom plete S equence Tim e
1 to 10,000
min.
F1
100 min.
S7
TRANSFER
READ/WRITE
1B80
Transfer Function
---
---
F56
Disabled
1B81
Transfer Delay This Source
0.0 to 10.0
s
F2
1.0 s
1B82
Transfer Delay Other Source
0.0 to 10.0
s
F2
3.0 s
1B83
Block Trip On Double Loss
---
---
F30
Disabled
S7
AUTORECLOSE SETUP - 760 ONLY
READ/WRITE
1BA0
Autoreclose Function
---
---
F30
Disabled
1BA1
Number of Reclosure Shots
1 to 4
1
F1
1
1BA2
Autoreclose Reset Time
1 to 1000
s
F1
60 s
1BA3
Autoreclose Block Time Upon Manual Close
0 to 200
s
F1
10 s
1BA4
Incomplete Sequence Time
1 to 1000
s
F1
30 s
1BA5
Reclosure Enabled Relays
---
---
F57
None
1BA6
Reclose In Progress Relays
---
---
F57
None
1BA7
Reclosure Lockout Relays
---
---
F57
None
1BA8
8
Autoreclose External Close Logic
---
---
F30
Disabled
S7
AUTORECLOSE RATE SUPERVISION - 760 ONLY
READ/WRITE
1BAA
8
Rate Supervision Function
---
---
F38
Disabled
1BAB
8
Max Autoreclose Rate
1 to 50
/hr.
F1
25
1BAC
8
Rate Supervision Relays
---
---
F57
None
S7
CURRENT SUPERVISION - 760 ONLY
READ/WRITE
1BB0
Current Supervision Function
---
---
F30
Disabled
1BB1
2
3 Shots For Current Above
0.00 to 20.00
x CT
F3
17.00 x CT
1BB2
2
2 Shots For Current Above
0.00 to 20.00
x CT
F3
18.00 x CT
1BB3
2
1 Shot For Current Above
0.00 to 20.00
x CT
F3
19.00 x CT
1BB4
Current Supervision To Lockout
---
---
F30
Disabled
Table 16–15: MODBUS MEMORY MAP (Sheet 37 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...