GE Power Management
750/760 Feeder Management Relay
16-
47
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
1836
1
Fault Type Output to Relays 4 to 7
---
---
F30
Disabled
1837
9
Fault Location After Trip
----
----
F30
Disabled
S6
CURRENT DEMAND
READ/WRITE
1840
Current Demand Function
---
---
F38
Disabled
1841
Current Demand Measurement Type
---
---
F58
Thermal Exp.
1842
Current Demand Thermal 90% Response
---
---
F16
15 min.
1843
Current Demand Time Interval
---
---
F16
20 min.
1844
Current Demand Relays
---
---
F57
None
1845
Current Demand Pickup
10 to 10000
A
F1
1000 A
S6
REAL POWER DEMAND
READ/WRITE
1848
Real Power Demand Function
---
---
F38
Disabled
1849
Real Power Demand Measurement Type
---
---
F58
Block Interval
184A
Real Power Demand Thermal 90% Response
---
---
F16
15 min.
184B
Real Power Demand Time Interval
---
---
F16
20 min.
184C
Real Power Demand Relays
---
---
F57
None
184D
2
Real Power Demand Pickup
1 to 30000
kW
F86
100 kW
S6
REACTIVE POWER DEMAND
READ/WRITE
1850
Reactive Power Demand Function
---
---
F38
Disabled
1851
Reactive Power Demand Measurement Type
---
---
F58
Block Interval
1852
Reactive Power Demand Thermal 90% Response
---
---
F16
15 min.
1853
Reactive Power Demand Time Interval
---
---
F16
20 min.
1854
Reactive Power Demand Relays
---
---
F57
None
1855
2
Reactive Power Demand Pickup
1 to 30000
kvar
F86
100 kvar
S6
APPARENT POWER DEMAND
READ/WRITE
1858
Apparent Power Demand Function
---
---
F38
Disabled
1859
Apparent Power Demand Measurement Type
---
---
F58
Block Interval
185A
App. Power Demand Thermal 90% Response
---
---
F16
15 min.
185B
Apparent Power Demand Time Interval
---
---
F16
20 min.
185C
Apparent Power Demand Relays
---
---
F57
None
185D
2
Apparent Power Demand Pickup
1 to 30000
kVA
F86
100 kVA
S6
5
PULSE OUTPUT
READ/WRITE
1860
Pulse Output Function
---
---
F38
Disabled
1861
Positive Watthours Pulse Output Relays
---
---
F57
None
1862
Positive Watthours Pulse Interval
0 to 65535
kWh
F86
100 kWh
1863
Negative Watthours Pulse Output Relays
---
---
F57
None
1864
Negative Watthours Pulse Interval
0 to 65535
kWh
F86
100 kWh
Table 16–15: MODBUS MEMORY MAP (Sheet 30 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...