750/760 Feeder Management Relay
GE Power Management
1.2 TECHNICAL SPECIFICATIONS
1 PRODUCT OVERVIEW
1
1.2.6 CONTROL
SYNCHROCHECK
Voltage Difference:
0.01 to 100.00 kV in steps of 0.01
Phase Difference:
0 to 100° in steps of 2°
Frequency Difference: 0.00 to 5.00 Hz in steps of 0.02
Bypass Permissives: DB & DL (Dead Bus and Dead Line)
LL & DB (Live Line and Dead Bus)
DL & LB (Dead Line and Live Bus)
DL | DB (Dead Line or Dead Bus)
DL X DB (Dead Line or Dead Bus,
but not both)
FOUR SETPOINT GROUPS
Can be changed from logic input or communications
Include protection features: Time O/C Curves, Phase O/C,
Neutral O/C, Ground O/C, Negative Sequence O/C &
Voltage, Phase Directional Control, Ground Directional
Control, Over & Undervoltage, Underfrequency and
Breaker Failure
UNDERVOLTAGE RESTORATION
Initiated By:
Trip from Undervoltage 1, 2, 3 or 4
Minimum Voltage
Level:
0.00 to 1.25 x VT in steps of 0.01
Time Delay:
0.1 to 100.0 in steps of 0.1 s
Incomplete Sequence
Time:
1 to 10000 in steps of 1 min.
Phases:
Any One/Any Two/All Three (pro-
grammable) phases have to operate
for output
Level Accuracy:
Per voltage input
Timing Accuracy:
± 100 ms
UNDERFREQUENCY RESTORATION
Initiated By:
Trip from Underfrequency 1 or 2
Minimum Voltage
Level:
0.00 to 1.25 x VT in steps of 0.01
Minimum Frequency
Level:
20.00 to 60.00 in steps of 0.01 Hz.
Time Delay:
0.1 to 100.0 in steps of 0.1 s
Incomplete Sequence
Time:
1 to 10000 in steps of 1 min.
Level Accuracy:
Per voltage and frequency input
Timing Accuracy:
± 100 ms
MANUAL CLOSE FEATURE BLOCKING
Set to operate by a manual close command.
Programmable to block instantaneous overcurrent ele-
ments for a selectable period.
Programmable to raise pickup of time overcurrent ele-
ments for a selectable period.
COLD LOAD PICKUP FEATURE BLOCKING
Set to operate automatically or by a logic input command.
Programmable to block instantaneous overcurrent ele-
ments for a selectable period.
Programmable to raise pickup of time overcurrent ele-
ments for a selectable period.
TRANSFER SCHEME
Used for double-bus system with two normally-closed
incoming and one normally-open bus tie circuit breaker.
Provides automatic closing of the bus tie breaker after a
loss of one source, with bus decayed voltage permissive.
Provides trip of a pre-selected breaker after the third
breaker is manually closed (prevent-parallel operation).
AUTORECLOSE (760 ONLY)
Up to four reclose attempts before lockout.
Each reclose shot can block instantaneous overcurrent,
and raise pickup of time overcurrent elements.
Current supervision can adjust the maximum number of
shots to be attempted.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...