GE Power Management
750/760 Feeder Management Relay
14-
37
14 S7 CONTROL
14.8 AUTORECLOSE (760 ONLY)
14
14.8.6 RECLOSURE SHOTS 1 TO 4
The following setpoints are programmed independently and are repeated for each of the Reclosure Shots 1-4.
These setpoints determine the dead time for a given shot and the overcurrent characteristics during that shot.
Selections for shots, that are greater than the maximum number of shots programmed in the scheme setup,
will not be used by the scheme.
■
RECLOSURE 1
■
[ENTER] for more
The Reclosure 1 setpoints path is:
\ SETPOINTS \ S7 CONTROL \ AUTORECLOSE \ RECLOSURE 1
DEADTIME BEFORE
RECLOSURE:
0.50 s
Range: 0.00 to 300.00 in steps of 0.01 s
Once the reclosure sequence has been initiated, selects the amount of time to wait before
closing the breaker.
PHASE INST OC 1
BLOCKING: Disabled
Range: Disabled, Enabled
Enable to block the Phase Instantaneous O/C 1 element while the reclose shot is in effect.
NEUTRAL INST OC 1
BLOCKING: Disabled
Range: Disabled, Enabled
Enable to block the Neutral Instantaneous O/C 1 element while the reclose shot is in effect.
GROUND INST OC
BLOCKING: Disabled
Range: Disabled, Enabled
Enable to block the Ground Instantaneous O/C element while the reclose shot is in effect.
SENSTV GND INST OC
BLOCKING: Disabled
Range: Disabled, Enabled
Enable to block the Sensitive Ground Instantaneous O/C element while the reclose shot is in
effect.
NEG SEQ INST OC
BLOCKING: Disabled
Range: Disabled, Enabled
Enable to block Negative Sequence Instantaneous O/C while the reclose shot is in effect.
PHASE TIME OC 1
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Phase Time O/C 1 element while the
reclose shot is in effect.
NEUTRAL TIME OC 1
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Neutral Time O/C 1 element while the
reclose shot is in effect.
GROUND TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Ground Time O/C element while the
reclose shot is in effect.
SENSTV GND TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Sensitive Ground Time O/C element
while the reclose shot is in effect.
NEG SEQ TIME OC
RAISED PICKUP:
0%
Range: 0 to 100 in steps of 1%
Selects the amount to raise the pickup level for the Negative Sequence Time O/C element
while the reclose shot is in effect.
SELECT SETPOINT
GROUP: Active
Range: Group 1, Group 2, Group 3, Group 4, Active Group
Select the setpoint group that will be used while the reclose shot is in effect. If Active Group
is selected then the active setpoint group is not affected. This setpoint provides enormous
flexibility in the autoreclose scheme.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...