12.7.4 LINE UNDERVOLTAGE
Line undervoltage 3 and 4 are identical protection elements that generate outputs in response to an undervolt-
age condition on the line voltage input. The time delay characteristic can be programmed as either definite time
or inverse time. A minimum operating voltage level is programmable to prevent undesired operation before
voltage becomes available. The setpoints for the Undervoltage 3 element are shown below. Undervoltage 4
setpoints are identical.
■
LINE UNDERVOLT 3
■
[ENTER] for more
The Line Undervoltage 3 setpoints path is:
\ SETPOINTS \ S5 PROTECTION \ VOLTAGE \ LINE UNDERVOLTAGE 3
LINE UNDERVOLTAGE 3
FUNCTION: Disabled
Range: Disabled, Trip, Alarm, Latched Alarm, Control
Select the required function.
LINE UNDERVOLTAGE 3
RELAYS (3-7): -----
Range: Any Combination of the 3-7 AUXILIARY Relays
Select the output relays required.
LINE UNDERVOLTAGE 3
PICKUP: 0.75 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
Selects the pickup as a fraction of the nominal bus VT Secondary Voltage. For
example, if the nominal VT secondary voltage is 120 V, and an alarm is
required whenever the voltage goes below 110 V, enter 110 / 120 =
0.92 x VT
for the pickup.
LINE UNDERVOLTAGE 3
CURVE: Definite Time
Range: Definite Time, Inverse Time
Selects the shape of the undervoltage time curve to be used.
Definite Time:
Time delay equal to the Bus Undervoltage 1 Delay setpoint.
Inverse Time:
See Section 12.1.4: IAC CURVES on page 12–4.
LINE UNDERVOLTAGE 3
DELAY:
2.0 s
Range: 0.0 to 6000.0 in steps of 0.1 s
Selects the minimum operating time of Line Undervoltage 3. If voltage is above
the pickup level or below the minimum operating voltage the timer resets.
MINIMUM OPERATING
VOLTAGE: 0.30 x VT
Range: 0.00 to 1.25 in steps of 0.01 x VT
The Line Undervoltage 3 element is inhibited for voltages below this level. Set-
ting this voltage to
0.00
will allow a dead bus to be considered a fault condition.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...