Option Manual
MFR 300 K55
Multifunction Relay
Release 1.0215
Document ID: B37933, Revision A - Build 51726
MFR 300
Страница 1: ...Option Manual MFR 300 K55 Multifunction Relay Release 1 0215 Document ID B37933 Revision A Build 51726 MFR 300...
Страница 2: ...Manual in English Designed in Germany Woodward GmbH Handwerkstr 29 70565 Stuttgart Germany Telephone 49 0 711 789 54 510 Fax 49 0 711 789 54 101 E mail stgt info woodward com Internet http www woodwar...
Страница 3: ...ions 5 1 2 Copyright And Disclaimer 6 1 3 Service And Warranty 6 2 Safety 8 2 1 Intended Use 8 2 2 Personnel 8 2 3 General Safety Notes 9 2 4 Protective Equipment And Tools 11 3 Configuration 12 3 1 N...
Страница 4: ...ons for option K55 in comparison to the MFR 300 standard device and documentation The following MFR 300 Technical Manual is a mandatory part of the Option K5 device description MFR 300 Technical Manua...
Страница 5: ...possibly dangerous situation that could cause slight injuries if it is not avoided NOTICE This combination of symbol and signal word indicates a possibly dangerous situation that could cause property...
Страница 6: ...the general terms and conditions the manufacturer s delivery conditions and the statutory regulations valid at the time the contract was concluded apply Copyright This manual is protected by copyrigh...
Страница 7: ...quire about the terms of warranty from your nearest Woodward representative For our contact search webpage please go to http www woodward com Directory aspx 7 MFR 300 K55 B37933 1 General Information...
Страница 8: ...age due to improper use Improper use of the multifunction relay unit may cause damage to the control unit as well as connected components Improper use includes but is not limited to Operation outside...
Страница 9: ...rical systems and resources cut the electricity and ensure it remains off for the duration of the work Comply with the five safety rules in the process cut electricity safeguard against restart ensure...
Страница 10: ...cabinets equipment etc to discharge any static electricity Alternatively wear an ESD wrist band connected to ground 4 Keep plastic vinyl and Styrofoam materials such as plastic or Styrofoam cups cigar...
Страница 11: ...personnel to wear protective equipment Specific required equipment is listed in each individual set of instructions The cumulative required personal protective equipment is detailed below Protective e...
Страница 12: ...1 to 2047 904 The COB ID of the TPDO 4 9951 COB ID 3 1 to 2047 905 The COB ID of the TPDO 5 9952 COB ID 3 1 to 2047 906 The COB ID of the TPDO 6 9953 COB ID 3 1 to 2047 907 The COB ID of the TPDO 7 9...
Страница 13: ...f the TPDO 5 A value of 0 means the TPDO is off A value of 1 240 means the number of SYNC messages which have to be received until the MFR300 sends a PDO A value of 254 or 255 means free running the M...
Страница 14: ...f the TPDO 8 A value of 0 means the TPDO is off A value of 1 240 means the number of SYNC messages which have to be received until the MFR300 sends a PDO A value of 254 or 255 means free running the M...
Страница 15: ...f the TPDO 11 A value of 0 means the TPDO is off A value of 1 240 means the number of SYNC messages which have to be received until the MFR300 sends a PDO A value of 254 or 255 means free running the...
Страница 16: ...f the TPDO 14 A value of 0 means the TPDO is off A value of 1 240 means the number of SYNC messages which have to be received until the MFR300 sends a PDO A value of 254 or 255 means free running the...
Страница 17: ...f the TPDO 16 A value of 0 means the TPDO is off A value of 1 240 means the number of SYNC messages which have to be received until the MFR300 sends a PDO A value of 254 or 255 means free running the...
Страница 18: ...1963 Underfrequency 2 triggered Mask 08h Bit 2012 Overvoltage 1 triggered Mask 10h Bit 2013 Overvoltage 2 triggered Mask 20h Bit 2062 Undervoltage 1 triggered Mask 40h Bit 2063 Undervoltage 2 trigger...
Страница 19: ...monitoring 4 triggered Mask 08h Bit LED 1 Mask 10h Bit LED 2 Mask 20h Bit Reserve 0 Mask 40h Bit Reserve 0 Mask 80h Bit 4 5 Relay 1 Mask 01h Bit Relay 2 Mask 02h Bit Relay 3 Mask 04h Bit Relay 4 Mask...
Страница 20: ...30Hz or higher than 80Hz it is set to zero This is a two s complement value and may be positive or negative 0 1 Hz sec 6 0 1 Current L1 This value is calculated new after every voltage cycle It is not...
Страница 21: ...be considered as zero PT Primary voltage 4000 V 8 4 5 Voltage L3 N This value is calculated new after every voltage cycle It is not filtered Values smaller than 1 5 of the PT primary voltage have to b...
Страница 22: ...t 1616 58 var 10 2 3 Reactive power L2 This value is calculated new after every voltage cycle of each phase It is not filtered If the voltage is lower than 1 5 of the PT primary voltage the reactive p...
Страница 23: ...20 Positive energy 0 1 kWh 11 4 5 6 7 2522 Positive reactive energy 0 1 kvarh 12 0 1 2 3 2524 Negative energy 0 1 kWh 12 4 5 6 7 2526 Negative reactive energy 0 1 kvarh 13 0 7 Reserve 0 14 0 7 Reserve...
Страница 24: ...Index C CAN PDO 12 Contact person 6 Customer Service 6 I Intended use 8 P Personnel 8 Protective equipment 11 S Service 6 Symbols in the instructions 5 U Use 8 W Warranty 7 24 MFR 300 K55 B37933 Index...
Страница 25: ...Woodward GmbH Handwerkstra e 29 70565 Stuttgart Germany Phone Fax stgt info woodward com 49 0 711 789 54 510 49 0 711 789 54 101...