CAN
Parameter
ID
Description
Multiplier Units
PDO
Data
byte
smaller than 1.5% of the PT primary voltage
have to be considered as zero.
7
4,5
203
Voltage L3-L1
This value is calculated new after every
voltage cycle. It is not filtered. Values
smaller than 1.5% of the PT primary voltage
have to be considered as zero.
PT
Primary
voltage /
4000
V
7
6,7
162
Angle wye voltage L1-L2
0.1
°
8
0,1
Voltage L1-N
This value is calculated new after every
voltage cycle. It is not filtered. Values
smaller than 1.5% of the PT primary voltage
have to be considered as zero.
PT
Primary
voltage /
4000
V
8
2,3
Voltage L2-N
This value is calculated new after every
voltage cycle. It is not filtered. Values
smaller than 1.5% of the PT primary voltage
have to be considered as zero.
PT
Primary
voltage /
4000
V
8
4,5
Voltage L3-N
This value is calculated new after every
voltage cycle. It is not filtered. Values
smaller than 1.5% of the PT primary voltage
have to be considered as zero.
PT
Primary
voltage /
4000
V
8
6,7
163
Angle wye voltage L2-L3
0.1
°
9
0,1
Active power L1
This value is calculated new after every
voltage cycle of each phase. It is not
filtered. If the voltage is lower than 1.5% of
the PT primary voltage, the power value has
to be considered as zero. This is a two's
complement value and may be positive or
negative.
PT
Primary
voltage *
CT
primary
current /
1616.58
W
9
2,3
Active power L2
This value is calculated new after every
voltage cycle of each phase. It is not
filtered. If the voltage is lower than 1.5% of
the PT primary voltage, the power value has
to be considered as zero. This is a two's
PT
Primary
voltage *
CT
primary
current /
1616.58
W
21
MFR 300 K55
B37933
4 Fixed TPDOs