Description

IEC 62061

SILCL

Safety relay for emergency stop, safety door and 
light grid monitoring with adjustable delay time

PSR-...-24DC/ESD/5X1/1X2/300

© PHOENIX CONTACT

Data sheet

The

PSR-...-24DC/ESD/5X1/1X2/300

 safety relay can be 

used for emergency stop, safety door and light grid monitor-
ing in safety circuits according to EN

60204-1.

Depending on the external wiring, up to category 

4, PL

e ac-

cording to EN

ISO

13849-1 or SILCL

3 according to 

EN

62061 can be achieved for the undelayed contacts and 

category

3, PL

d according to EN

ISO

13849-1 or SILCL

2

can be achieved for the dropout delayed contacts.

Control is via a single channel or two channels, either with 
automatic or manual start circuit.

A connected reset button is monitored.

The safety relay is equipped with three enabling current 
paths and one signaling current path that drop out without 
delay according to stop category

0.

Two other enabling current paths drop out with a delay in 
compliance with stop category 1.

The delay time is set in 24

increments via the rotary switch 

and the DIP switch in the upper housing part.

Features

Emergency stop, safety door and light grid monitoring

Undelayed contacts suitable up to category

4, PL

e

(EN

ISO

13849-1), SILCL

3 (EN

62061)

Dropout delayed contacts suitable up to category 3, 
PL

d (EN

ISO 13849-1), SILCL

2 (EN

62061)

Single or two channel operation

Automatic or manual start circuit

3 undelayed enabling current paths

2 delayed enabling current paths

1 undelayed signaling current path

Adjustable delay time (0.2

s

...

300

s, 24

increments)

Option of screw or spring-cage terminal blocks for plug-
in

WARNING: Risk of electric shock

Observe the safety instructions in the corresponding section!

Make sure you always use the latest documentation.
It can be downloaded from the product at 

phoenixcontact.net/products

.

This data sheet is valid for all products listed on the following pages.

102104_en_03

2015-05-11

www.phoenixpowersupply.co.uk

Содержание 2981428

Страница 1: ...ding to stop category 0 Two other enabling current paths drop out with a delay in compliance with stop category 1 The delay time is set in 24 increments via the rotary switch and the DIP switch in the upper housing part Features Emergency stop safety door and light grid monitoring Undelayed contacts suitable up to category 4 PL e EN ISO 13849 1 SILCL 3 EN 62061 Dropout delayed contacts suitable up...

Страница 2: ...ting and indication elements 8 8 1 Connection assignment 8 9 Diagnostics 8 10 Function 9 11 Configuration 9 11 1 Setting the delay time 9 11 2 Protection against manipulation 9 12 Application examples 10 12 1 Single channel emergency stop monitoring 10 12 2 Two channel emergency stop monitoring 10 12 3 Two channel safety door monitoring 10 12 4 Light grid monitoring automatic start 10 www phoenixp...

Страница 3: ... 1 Typical input current 155 mA DC Voltage at input start and feedback circuit approx 24 V DC Max permissible overall conductor resistance Input and reset circuit at UN 22 ǥ Input and start circuits at UN Typical response time 70 ms manual start 600 ms Auto start Typical release time 20 ms undelayed contacts Recovery time 1 s Output data Contact type 3 enabling current paths undelayed 2 enabling c...

Страница 4: ...ns Screw connection Spring cage connection W x H x D 45 x 99 x 114 5 mm 45 x 112 x 114 5 mm Connection data Screw connection Spring cage connection Conductor cross section solid 0 2 mm 2 5 mm 0 2 mm 1 5 mm Conductor cross section stranded 0 2 mm 2 5 mm 0 2 mm 1 5 mm Conductor cross section AWG kcmil 24 12 24 16 Stripping length 7 mm 8 mm Ambient conditions Ambient temperature operation 20 C 55 C A...

Страница 5: ...onths Duration of use 240 Months Safety characteristic data according to EN ISO 13849 Category 4 Undelayed contacts Performance level e for dropout delay contacts PL d CCF Passed Duration of use 240 Months Data only applies if the safety function is demanded at least once a year and the signal contact is read back The specifications apply assuming the following calculation basis B10d 230000 At 3 A...

Страница 6: ...1 Y2 Feedback circuit S10 S11 S12 S21 S22 Input circuits S33 S34 S35 Start circuit 13 14 Undelayed enabling current paths 23 24 33 34 41 42 Signaling current path 57 58 Delayed enabling current paths 67 68 A1 Y1 Y2 S10S11 S12 13 23 33 41 57 K1 K2 K3 K4 Logic A2 S33S34 S35 S21 S22 14 24 34 42 58 68 67 T A C I A TH 2 2 10 20 30 40 0 10 20 30 40 50 60 0 45 55 50 60 70 80 55 www phoenixpowersupply co ...

Страница 7: ...WARNING Danger due to faulty devices The devices may be damaged following an er ror and correct operation can no longer be en sured In the event of an error replace the device im mediately Repairs to the device especially if the hous ing must be opened may only be carried out by the manufacturer or authorized persons Otherwise the warranty is invalidated NOTE Risk of damage to equipment due to inc...

Страница 8: ... 3 5 3 3 3 4 2 3 2 4 1 3 1 4 P S R E S D 3 0 0 A 1 S 2 1 S 2 2 A 2 S 1 0 S 1 1 S 1 1 S 1 2 Y 1 Y 2 5 8 6 8 4 2 5 7 6 7 4 1 P o w e r K 1 K 2 K 3 t K 4 t 1 2 T i m e B A o n 1 6 3 4 5 2 A 2 APPROVALS 13 23 33 41 57 58 14 24 34 42 58 68 1 2 3 4 5 6 0 2 0 4 0 8 1 6 2 4 3 2 4 4 8 6 4 12 8 19 2 50 100 150 200 250 300 0 6 0 8 1 1 2 25 32 38 on 1 2 3 4 5 6 7 8 15 14 13 9 10 12 11 Designation Explanation ...

Страница 9: ...ch and the DIP switch in the upper housing part 1 Set a time period using the DIP switches 2 Set the desired delay time with the rotary switch Figure 4 Configuring the time delay 11 2 Protection against manipulation Once the time has been set the rotary switch and the DIP switch can be protected against manipulation by covering with the label provided Figure 5 Applying the label Once configuration...

Страница 10: ...al monitored start 12 4 Light grid monitoring automatic start Automatic start Monitoring of external contactors Suitable up to category 4 PL e EN ISO 13849 1 SILCL 3 EN 62061 Figure 9 Light grid monitoring automatic start For an automatic start bridge contacts S33 and S35 as well as Y1 and Y2 K3 K4 Y Y 2 1 S1 M N L1 L K3 K4 A1 23 33 13 41 A2 S33 S34 S35 24 34 14 42 PSR ESD 5x1 1x2 S S S 12 11 10 S...

Отзывы: