Application Guide 

Volume VIII  AG2015-33 

Basic Feeder Protection Using SEL-849 

Factory Logic 

Anthony Rahiminejad

 

I

NTRODUCTION

 

The SEL-849 Motor Management Relay offers advanced low-voltage motor protection in a 

compact and economical design, but it can also be used to provide basic feeder protection for a 

variety of applications. 
This application guide demonstrates how to configure the SEL-849 to provide overcurrent 

protection for a feeder protection application. 

F

ACTORY 

D

EFAULT 

L

OGIC 

C

ONNECTION

 

Figure 1 shows the connection diagram for factory default I/O assignments for feeder protection 

using the SEL-849. 

52

A

B

C

SEL-849

Select 

Control 

Mode

Remote

Close

Open

52A

B9

IN06

B8 

COM 

0506

B7 

IN05

B6 

IN04

B5 

COM 

0304

B4 

IN03

B3 

IN02

B2 

COM 

0102

B1 

IN01

E4

E1

OUT01

OUT02

E2

E3

E5

52B

52A

A2

A3

–/N

+/H

IA

IB

IC

Source

Load

Feeder

Settings:

APP := FEEDER

CURR_IN := NORMAL

FACTLOG := Y

OUT01 = (TRIP OR STOP) (Hidden)

OUT02 = STR_CLO (Hidden)

OUT03 = (50PAF OR 50GAF) AND TOL1 (available for user)

OUT04 = HALARM OR SALARM (available for user)

TC

CC

 

Figure 1  Connection Diagram for Factory Default I/O Assignments for Feeder Application 

C

ONFIGURE THE 

SEL-849

 FOR 

B

ASIC 

F

EEDER 

P

ROTECTION

 

The example settings used in this section are for a 1,200 A feeder supplying a 480 V switchboard. 

Perform the following steps to configure the SEL-849. 

Step 1 

Connect the computer to PORT2A or PORT2B of the relay using an Ethernet cable. Check the 

LED for connectivity status. 