background image

Date Code 20151102 

 

SEL Application Guide 2015-33 

Step 4 

From the drop-down menu on the left-hand side of the page, select 

Settings

 > 

Protection

 > 

Basic 

Settings

. The rated frequency and phase rotation should be set based on the power system. In this 

example, the SEL-849 is applied on a 60 Hz power system with ABC phase rotations. 

Application (APP)

 should be set to 

FEEDER

. See Figure 4 for an example of basic settings for a 

feeder application. 

 

Figure 4  Basic Settings 

Step 5 

In this example, the nominal feeder current is 1,200 A, which exceeds the 128 A limit of the 

integrated Rogowski coil current transformers (CTs). External CTs must be used, where the 

external CT leads are passed through the CT inputs of the SEL-849. When using external CTs, 

divide the CT primary by the CT secondary. Enter this value into 

Phase CT Ratio 1 (CTR1)

. If a 

core balance CT is used for ground fault sensing, 

Core Balance CT Ratio (CTRN)

 should be set 

equal to the core balance CT ratio, and modifications to the factory logic will be required. Set 

Full Load Amps (FLA1)

 equal to the current rating of the feeder to be protected divided by the 

Phase CT Ratio 1 (CTR1) value

 (see Figure 4). In this example, 1200/5 external CTs are used 

and the current rating of the feeder is 1,200 A.  
Note that the SEL-849 includes optional voltage, power, and arc-flash protection and control 

elements that are not discussed in this application guide. Refer to the SEL-849 Instruction Manual 

for additional details. 

Отзывы: