Function

Set the nominal input voltage to A1 and A2 - the power LED 
lights up.

Now a voltage of 24 V DC is available at terminals S11 and 
S21 that monitors itself for cross circuit.

Wire S12 and S22 according to the corresponding connec-
tion examples.

Bridge terminals S33 and S35 for automatic activation. The 
safety relay starts automatically after the safety door closes.

The contacts 13/14, 23/24, 33/34, 57/58, 67/68 close and 
the signal contact 41/42 opens. The LEDs K1, K2, K3(t) and 
K4(t) light up.

If the input circuit is opened, relays K1 and K2 switch off 
without delay and the LEDs extinguish. Relay K3t and K4t 
switch off with delay.

To reactivate the safety relay, close the input circuits and 
press the Reset button, if exists.

11

Configuration

To configure the safety relay, proceed as follows:

1

Disconnect the safety relay from the supply voltage.

2

Set the delay time (0,2

s ... 300

s).

3

Restore the power supply.

4

Close the emergency stop circuits.

5

In the case of a 

manual start:

 press the reset button.

6

Automatic start circuit:

 wait for the configured delay 

time until the enabling current paths are closed and the 
Power LED lights up.

7

Manual start circuit:

 wait for the configured delay time 

and press the reset button until the enabling current 
paths are closed and the Power LED lights up.

11.1

Setting the delay time

The delay time of 0.2

s to 300

s is set in 24

increments via 

the rotary switch and the DIP switch in the upper housing 
part.

1

Set a time period using the DIP switches.

2

Set the desired delay time with the rotary switch.

Figure 4

Configuring the time delay

11.2

Protection against manipulation

Once the time has been set, the rotary switch and the DIP 
switch can be protected against manipulation by covering 
with the label provided.

Figure 5

Applying the label

Once configuration is complete, close the four 
enable current paths and the Power, K1/K2 
and K3(t)/K4(t) LEDS are illuminated.

WARNING: Danger due to incorrect delay 
time!

Check the set delay time following installation.

If the rotary switch is modified during opera-
tion, the safety relay switches to configuration 
mode and the LEDs flash. The safety relay is 
only ready for operation again once the supply 
voltage has been switched off and on again 
and configuration has been carried out.

1 2

3

4

5

6

B

A

B

A

B

A

B

A

on

1

0

,

2

0

,8

6

,4

5

0

2

0

,4

1

,

6

12

,8

100

3

0

,

6

2

,4

1

9,

2

1

5

0

4

0

,8

3,

2

2

5

200

5

1

4

3

2

2

5

0

6

1

,

2

4,8

38

3

00

58

68

42

23

24

13

33

34

14

57

58

41

S

12

S

34

S

33

S

35

33

34

23

24

13

14

P

S

R-E

S

D-30

0

A1

S

21

S

22

A2

S

10

S

11

S

11

S

12

Y1

Y2

58

68

42

57

67

41

Power

K1

K2

K3(t)

K4(t)

1

2

Tim

e

B

A

on

1

6

3

4

5

2

P

S

R-

SC

P-
24D

C

/E

S

D/5X1/1X2/300

Order

No.:

2

98

1

4

2

8

APPROVALS

Serial

No.

13

23

33

41

57

58

14

24

34

42

58

68

12

3456

0,2

0,4

0,8

1,6

2,4

3,2

4

4,8

6,4
12,8

19,2

50

100

150

200

250

300

0,6

0,8

1

1

,2

25

32

38

on

S

12

S

34

S

33

S

35

33

34

23

24

13

14

P

S

R-E

S

D-300

A1

S

21

S

22

A2

S

10

S

11

S

11

S

12

Y1

Y2

58

68

42

57

67

41

Pow

er

K1

K2

K3(t)

K4(t)

www.phoenixpowersupply.co.uk

Содержание 2981428

Страница 1: ...ding to stop category 0 Two other enabling current paths drop out with a delay in compliance with stop category 1 The delay time is set in 24 increments via the rotary switch and the DIP switch in the upper housing part Features Emergency stop safety door and light grid monitoring Undelayed contacts suitable up to category 4 PL e EN ISO 13849 1 SILCL 3 EN 62061 Dropout delayed contacts suitable up...

Страница 2: ...ting and indication elements 8 8 1 Connection assignment 8 9 Diagnostics 8 10 Function 9 11 Configuration 9 11 1 Setting the delay time 9 11 2 Protection against manipulation 9 12 Application examples 10 12 1 Single channel emergency stop monitoring 10 12 2 Two channel emergency stop monitoring 10 12 3 Two channel safety door monitoring 10 12 4 Light grid monitoring automatic start 10 www phoenixp...

Страница 3: ... 1 Typical input current 155 mA DC Voltage at input start and feedback circuit approx 24 V DC Max permissible overall conductor resistance Input and reset circuit at UN 22 ǥ Input and start circuits at UN Typical response time 70 ms manual start 600 ms Auto start Typical release time 20 ms undelayed contacts Recovery time 1 s Output data Contact type 3 enabling current paths undelayed 2 enabling c...

Страница 4: ...ns Screw connection Spring cage connection W x H x D 45 x 99 x 114 5 mm 45 x 112 x 114 5 mm Connection data Screw connection Spring cage connection Conductor cross section solid 0 2 mm 2 5 mm 0 2 mm 1 5 mm Conductor cross section stranded 0 2 mm 2 5 mm 0 2 mm 1 5 mm Conductor cross section AWG kcmil 24 12 24 16 Stripping length 7 mm 8 mm Ambient conditions Ambient temperature operation 20 C 55 C A...

Страница 5: ...onths Duration of use 240 Months Safety characteristic data according to EN ISO 13849 Category 4 Undelayed contacts Performance level e for dropout delay contacts PL d CCF Passed Duration of use 240 Months Data only applies if the safety function is demanded at least once a year and the signal contact is read back The specifications apply assuming the following calculation basis B10d 230000 At 3 A...

Страница 6: ...1 Y2 Feedback circuit S10 S11 S12 S21 S22 Input circuits S33 S34 S35 Start circuit 13 14 Undelayed enabling current paths 23 24 33 34 41 42 Signaling current path 57 58 Delayed enabling current paths 67 68 A1 Y1 Y2 S10S11 S12 13 23 33 41 57 K1 K2 K3 K4 Logic A2 S33S34 S35 S21 S22 14 24 34 42 58 68 67 T A C I A TH 2 2 10 20 30 40 0 10 20 30 40 50 60 0 45 55 50 60 70 80 55 www phoenixpowersupply co ...

Страница 7: ...WARNING Danger due to faulty devices The devices may be damaged following an er ror and correct operation can no longer be en sured In the event of an error replace the device im mediately Repairs to the device especially if the hous ing must be opened may only be carried out by the manufacturer or authorized persons Otherwise the warranty is invalidated NOTE Risk of damage to equipment due to inc...

Страница 8: ... 3 5 3 3 3 4 2 3 2 4 1 3 1 4 P S R E S D 3 0 0 A 1 S 2 1 S 2 2 A 2 S 1 0 S 1 1 S 1 1 S 1 2 Y 1 Y 2 5 8 6 8 4 2 5 7 6 7 4 1 P o w e r K 1 K 2 K 3 t K 4 t 1 2 T i m e B A o n 1 6 3 4 5 2 A 2 APPROVALS 13 23 33 41 57 58 14 24 34 42 58 68 1 2 3 4 5 6 0 2 0 4 0 8 1 6 2 4 3 2 4 4 8 6 4 12 8 19 2 50 100 150 200 250 300 0 6 0 8 1 1 2 25 32 38 on 1 2 3 4 5 6 7 8 15 14 13 9 10 12 11 Designation Explanation ...

Страница 9: ...ch and the DIP switch in the upper housing part 1 Set a time period using the DIP switches 2 Set the desired delay time with the rotary switch Figure 4 Configuring the time delay 11 2 Protection against manipulation Once the time has been set the rotary switch and the DIP switch can be protected against manipulation by covering with the label provided Figure 5 Applying the label Once configuration...

Страница 10: ...al monitored start 12 4 Light grid monitoring automatic start Automatic start Monitoring of external contactors Suitable up to category 4 PL e EN ISO 13849 1 SILCL 3 EN 62061 Figure 9 Light grid monitoring automatic start For an automatic start bridge contacts S33 and S35 as well as Y1 and Y2 K3 K4 Y Y 2 1 S1 M N L1 L K3 K4 A1 23 33 13 41 A2 S33 S34 S35 24 34 14 42 PSR ESD 5x1 1x2 S S S 12 11 10 S...

Отзывы: