background image

EB3N Safety Relay Barriers

Build a safety system in an explosive atmosphere.

• Ensures explosion protection safety and machine safety in an explosive 

atmosphere.

• Machine safety system can be built in compliance with ISO13849-1 Category 

4, Performance level e.

• Safety input devices applicable in any explosive gas and hazardous areas are 

available.

• Available with auxiliary inputs (5 points) used to monitor the operating status 

of safety input devices.

• A wide variety of Japan TIIS-rated emergency stop switches and interlock 

switches are available.

• Global usage 

Explosion protection: Global: PTB (IEC Ex), Europe: PTB (ATEX), USA: UL 

 

Japan (TIIS), China (Ex-CCC) 

Machine safety: 

TÜV Rheinland

• No grounding required.

Explosion 

Protection

Safety relay barrier [Exia] II C
Switch (EB9Z-A)

Exia II CT6

Switch (EB9Z-A1)

Exia II BT6

Safety  

Performance

Performance level e

Category 4

Safety Relay Barriers 

Safety Input Points Safety Output 

Points

Auxiliary Input Points  

(Note 1)

Auxiliary Output Points  

(Relay Output)

Reset (Start)

(Note 2, Note 3)

Part No.

2

2NO

Without

Without

Auto reset (Auto start)

EB3N-A2ND

Manual reset (Manual start)

EB3N-M2ND

2

2NO

5 (1 common)

5NO (1 common)

Auto reset (Auto start)

EB3N-A2R5D

Manual reset (Manual start)

EB3N-M2R5D

Note 1:  A maximum of five monitor contacts from safety input devices can be connected to the auxiliary input terminals. In addition, non-safety input devices can also be connected to the 

auxiliary input terminals.

Note 2:  On auto reset (auto start) models, when the safety condition is met (two safety inputs are both on), safety outputs are turned on automatically. 

Connect the reset (start) input terminals Y1 and Y2 together except for the following cases: 

When connecting a contactor or force guided relay to the safety output of the EB3N, connect the NC contacts of the contactor or force guided relay to the reset (start) input terminals 

Y1 and Y2 of the EB3N for use as a backcheck input signal.

Note 3:  On manual reset (manual start) models, while the safety condition is met (two safety inputs are both on), safety outputs are turned on at the falling edge of the reset switch (start 

switch) signal (OFF   ON   OFF) (start off check). 

Manual reset (manual start) models have a monitoring function of reset switch contacts (detection of welded contacts). Use NO contacts of a momentary switch for the reset (start) 

input. When connecting a contactor or force guided relay to the safety output of the EB3N, connect the NC contacts of the contactor or force guided relay to the reset (start) input 

terminals Y1 and Y2 of the EB3N for use as a backcheck input signal.

Selection Guide

1.  Selecting the reset (start) function

  Auto reset (auto start): 

Select this model when connecting safety control devices, such as safety relay modules or safety controllers, to the EB3N safety outputs to set up a safety 

system, using the reset (start) function of the safety control device.

   

Select this model when connecting contactors or force guided relays to the EB3N safety outputs to set up a safety system, and a risk assessment on the entire 

system has not found any safety problem in using auto reset (auto start).

  Manual reset (manual start): Select this model when connecting contactors or force guided relays to the EB3N safety outputs to set up a safety system, and a risk assessment on the entire 

system has found that manual reset (manual start) is necessary.

2.  Selecting the auxiliary outputs

  Without auxiliary outputs:    Select this model when the operating status of safety input devices are not monitored.

  With auxiliary outputs: 

  Select this model when the operating status of safety input devices are monitored or when non-safety input devices are also connected.

General Specifications

Rated Power Voltage

24V DC

Power Voltage Range

20.4 to 26.4V DC

Operating Temperature

–20 to +60°C (no freezing)

UL: –20 to +40°C  

(no freezing)

Operating Humidity

45 to 85% RH  

(no condensation)

Power  

Consumption

Without auxiliary output

5.5W maximum

With auxiliary output

7.0W maximum

Safety  

Output

Contacts

13-14, 

23-24

2NO

Rated Load

Resistive

30V DC, 1A

Inductive

DC-13, 24V, 1A

Response

(rated voltage)

Turn on

100 ms maximum

Turn off

20 ms maximum

Auxiliary  

Output

Contacts

A* - C1

5NO/1 common

Rated Load

Resistive

24V DC, 3A,  

common terminal 5A max.

Response

(rated voltage)

Turn on

15 ms maximum

Turn off

10 ms maximum

Mounting

DIN rail or panel mounting

*: Channel Nos. 1 to 5

Explosion-Protection Specifications

Explosion Protection

[Exia] II C

Non-intrinsically Safe Circuit Maximum Voltage 

(Um)

250V (UL: 125V)

Intrinsically Safe Circuit Maximum Voltage (Uo)

13.2V

Intrinsically Safe Circuit Maximum Current (Io)

227.2 mA

Intrinsically Safe Circuit Maximum Power (Po)

750 mW

Intrinsically Safe Circuit Allowable Capacitance (Co) 0.49 µF (TIIS: 0.28 μF)

Intrinsically Safe Circuit Allowable Inductance (Lo)

0.60 mH  

(TIIS: 0.56 mH)

Intrinsically Safe Circuit 

Wiring Resistance (Rw)

Safety circuit

(Note 1)

Auxiliary circuit

(Note 2) 

Note 1: 10Ω maximum (500m maximum using a 1.25 mm2 cable) 

Note 2: 600/(N+1)Ω maximum, where N = the number of common channels

Safety Specifications

Category

4

Performance Level (PL)

e

Mean Time to Dangerous Failure (MTTFd)

100 years

Diagnostic Range

99% minimum

Calculation conditions for MTTFd

 t

cycle

:  Mean operation cycle = 1 hour

 h

op

:  Mean operation hours per day = 24 hours

 d

op

:  Mean operation days per year = 365 days

Note: When t

cycle

 is shorter than 1 hour, MTTFd

 

 will decrease.

1

EB3N

  

Safety Relay Barriers

Содержание EB3N

Страница 1: ...cting the reset start function Auto reset auto start Select this model when connecting safety control devices such as safety relay modules or safety controllers to the EB3N safety outputs to set up a safety system using the reset start function of the safety control device Select this model when connecting contactors or force guided relays to the EB3N safety outputs to set up a safety system and a...

Страница 2: ... A2R5D Monitor Monitor Barrier Safety Output Auxiliary Output Monitor Output Reset Start Input Auxiliary Output Monitor Output EB3N M2R5D Barrier Safety Output Hazardous Area Non hazardous Area Hazardous Area Non hazardous Area A safety relay module or safety controller is used to set up a safety circuit using the reset start function of the safety relay module or safety controller The manual rese...

Страница 3: ...rents connect an IEC60127 2 compliant 2A fast blow fuse 5 20 mm 11 Evaluate the ISO 13849 1 category and performance level in consideration of the entire system Notes for Explosion Protection Safety 1 Install the EB3N in an enclosure capable of protecting against mechanical shocks at a hazardous location in accordance with intrinsic safety ratings and parameters 2 Install and wire the EB3N so that...

Страница 4: ...in the above applications be sure to consult with an IDEC sales representative 3 Inspections We ask that you implement inspections for IDEC products you purchase without delay as well as thoroughly keep in mind management maintenance regarding handling of the product before and during the inspection 4 Warranty 1 Warranty period The warranty period for IDEC products shall be one 1 year after purcha...

Отзывы: