background image

PR102.24.2.2_3-EN-80145-1.4
© All rights reserved. Subject to technical changes and misprints.

akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany

Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de

PR102.24.2.2

Programmable relay

WARNING

Switch off the supply voltage before working on the relay or
connecting or disconnecting it with other devices or PC. Switch the
supply voltage on only after all works has been completed.

CAUTION

The program runs after transferring it to the relay. It is recommended
to transfer the program before wiring the relay. Otherwise ensure that
all peripheral devices are disconnected from relay outputs before
transferring the program.

1. Specifications

Table 1

General specification

Power supply

24 (9…30) V DC

Power consumption, max.

8 W

Galvanic isolation

no

Reverse polarity protection

yes

Inputs

Digital

16

Analog

8

Outputs

Digital

14

Analog

2

Network interface

2 × RS485

Protocol

Modbus-RTU, Modbus-ASCII

Mode

Master/Slave

Baud rate

9.6…115.2 kbit/s

Galvanic isolation

1500 V / 1 s

Extension modules

up to 2 PRM

Real-time clock accuracy

± 3 s / day

Backup battery

CR2032

Dimensions (with terminal blocks)

123 × 108 × 58 mm

Mounting

DIN-rail (35 mm)

Weight

approx. 250 g

Table 2

Digital inputs

HIGH level

8.5…30 V / 2…5 mA

LOW level

-3…+5 V / 0…15 mA

Pulse length, min.

5 ms

Response time, max.

30 ms

Pulse frequency, max.

200 Hz

Galvanic isolation

no

Table 3

Analog inputs

ADC resolution

12 bit

Sampling time, max.

1 ms

Galvanic isolation

no

Analog mode 1 (Linear input)

Input signal

0-10 V, 4-20 mA, 0-300 kΩ

Input resistance for 0-10 V input

10 kΩ

Basic error

±0.5 %

Temperature influence

±0.5 % / 10 °C

Analog mode 2 (Temperature sensors)

Input signal

see Tab. 4

Least significant bit value

1 °C

Basic error

PTC thermistors

±1.5 %

NTC thermistors

±1.0 %

Temperature influence

±0.5 % / 10 °C

Digital mode

Nominal input voltage

24 V DC

HIGH/LOW threshold
(adjustable in ALP)

2.5…10 V

LOW/HIGH threshold
(adjustable in ALP)

3…10.5 V

Pulse length, min.

5 s

Signal frequency, max.

100 Hz

Table 4

Sensors (analog mode 2)

Sensor

Measurement range

RTD

Pt 500 (α = 0.00385 °С

−1

)

–200…+850 °С

500P (α = 0.00391 °С

−1

)

–200…+850 °С

Cu 500 (α = 0.00426 °С

−1

)

–50...+200 °С

500M (α = 0.00428 °С

−1

)

–180...+200 °С

Ni500 (α = 0.00617 °С

−1

)

–60...+180 °С

Cu 1000 (α = 0.00426 °С

−1

)

–50...+200 °С

1000M (α = 0.00428 °С

−1

)

–180...+200 °С

Pt 1000 (α = 0.00385 °С

−1

)

–200...+850 °С

1000P (α = 0.00391 °С

−1

)

–200...+850 °С

Ni 1000 (α = 0.00617 °С

−1

)

–60...+180 °С

Thermistors / NTC

B57861S series, 2 kΩ, B

25/100

= 3560K

–55…+100 °С

Sensor

Measurement range

B57861S series, 3 kΩ, B

25/100

= 3988K

–55…+145 °С

B57861S series, 5 kΩ, B

25/100

= 3988K

–35…+145 °С

B57861S series, 10 kΩ, B

25/100

= 3988K

–35…+155 °С

B57861S series, 30 kΩ, B

25/100

= 3964K

–20…+155 °С

B57861S series, 50 kΩ, B

25/100

= 3760K

–10…+155 °С

NTC 3435, 10 kΩ

–40…+105 °С

NTC 3977, 10 kΩ

–40…+125 °С

Thermistors / PTC

KTY82-110

–55…+150 °С

KTY82-120
KTY82-121
KTY82-122
KTY82-150
KTY82-151

Table 5

Digital outputs

Type

relay (NO)

Switching capacity

AC

5 A, 250 V AC (resistive load)

DC

3 A, 30 V DC

Load current at 5 V DC, min.

10 mA

Service life, electrical

AC

200,000 switching cycles

DC

100,000 switching cycles

Galvanic isolation

individual

between outputs

1780 V

against other circuits

2300 V

Table 6

Analog outputs

Output signal

4-20 mA, 0-10 V

External voltage supply

15…30 V

Basic error, max.

±0.5%

Temperature influence

±0.5% / 10°C

DAC resolution

12 bit

Load
resistance

R

I

(4-20 mA), max.

300 Ω

R

U

(0-10 V), min.

1 kΩ

Galvanic isolation

510 V / 1 s, individual

2. Operating conditions

The device is designed for natural convection cooling.
The following environmental conditions must be observed:
• clean, dry and controlled environment, low dust level
• closed non-hazardous areas, free of corrosive or flammable gases

Table 7

Operating conditions

Condition

Permissible range

Operating temperature

-40…+55 °C

Relative humidity

up to 80 % (at +25 °C, non-condencing)

Attitude

up to 2000 m above sea level

IP code

IP20

EMC immunity

conforms to IEC 61000-6-2

EMC emission

conforms to IEC 61000-6-4

3. Installation

Fig. 1

Dimensions

Fig. 2

Installation:

1.

Place the device on a DIN rail as shown in

Fig. 2

.

2.

Press the device firmly against the DIN rail in the direction of arrow 2
until the latch locks.

Отзывы: