background image

 

 

 

 

 

TR-42 Temperature Protection Relay

 

1

 

Instruction Manual: TR42 GBM 25/02/2021

 

 

1.

 

DESCRIPTION 

The  digital  temperature  relay  TR-42  has  been  created  as  an  accessory  of  main  importance  for  resin  or  air  insulated  three-phase  MT  transformers,  as 
protection against dangerous over temperatures on the insulating coil, on the winding and to manage the intervention of cooling fans.  The temperature is 
detected by 3 or 4 thermal detectors PT 100, three of them located in the transformer coils, the fourth on the core. 

 
Features 

-

 

Display of the actual temperature of the 4 PT sensors. 

-

 

Display & storage of the highest temperature of each PT sensor. 

-

 

3 programmable output contacts from 0° to 220°C level 1, level 2 and FAN 
control. 

-

 

Automatic and “Always ON” fan mode.

 

-

 

Alarm of device failure or PT 100 disconnection or short circuit. 

-

 

Automatic fan start every week (bearing protections). 

-

 

Insulated RS-485 communication port. 

-

 

Insulated 4-20mA output 

(Optional: see ORDER CODE)

2.

 

INSTALLATION 

Install the equipment according to the characteristics of humidity and temperature that has been designed to work in. To avoid noise pickup and interference 
the relay should be placed away from high current conductors or sources of strong magnetic fields. The device has been designed for the installation on a 
panel board with a cutout of 92x92mm using the fixing accessories that come with the relay. Before proceeding with the installation that must be carried 
out by a qualified technician, it is recommended to disconnect the power supply on the working area. Orion Italia urges that security procedures be followed 
during this installation. 
 

3.

 

WIRING CONNECTION 

For the connection, follow the diagram on page 4. Herein after the description of the different electric connections: 
 

3.1

 

POWER SUPPLY 

The power supply range is: 24-240 Vcc/Vca (50 

 60Hz), -15%, +10% and power must be connected between the terminals 40 and 42. Note: The device does 

not have internal fuses. This is to allow the selection of the desired external protection. 
IMPORTANT: before doing the dielectric strength test of panel board, where the  device is installed, it is necessary to disconnect it from the power line 
voltage. 

3.2

 

SENSORS CONNECTION 

Each PT sensor has one white wire and two red ones according to the UNI 7937 regulation. 

-  Sensor  cables  should  be  made  with  shielded  twisted  pairs  and  the 

shield should be connected to the system’s ground.

 

- To compensate the resistance of the wire, it is necessary to connect 
each sensor with three (3) wires of the same section (at least 1 mm²). 

- The probes wiring should be placed away from high current conductors, 
high tension and from inductive elements such as  remote-control switch, 
etc. If the wires travel on the same route as the power lines, separate the 
wires with suitable elements. 

3.3

 

OUTPUT CONTACTS CONNECTION 

In the back side of the device, it is possible to see the output contacts (in absence of power supply). The ALARM relay (L1), TRIP relay (L2) and fan control 
(FAN) activate when temperature reaches the setpoint. The FAULT relay (FAULT) opens when power supply is connected and it will be closed when internal 
failure occurs, failure of the PT sensors or failure of the power supply. The FAN contact can be used as a control of the cooling system. Note: When using 
the contacts for control of inductive loads in Vac (coils of relays, contactors, solenoids), it is essential to limit the overcurrent, or place a R/C group in parallel 
to the inductor. If it works in DC, a diode in anti-parallel should be connected. 

3.4

 

SERIAL COMMUNICATION CONNECTION 

Communication capabilities are available in the device connecting the RS-485 port in a network (up to 32 devices) controlled by a supervisor device (PC). 
The protocol used is Modbus RTU. The connections must be made with shielded twisted wires. 
 

4.

 

FUNCTIONS AND SIGNALS 

Display:

 on the display °C (3 digits) you can observe the value of the temperature and program the settings; through the display PT (1 digit) you can see the 

corresponding Pt Channel. 

SET LED:

 if on, it indicates that the user is in the SET mode. 

°C MAX LED:

 if on, it indicates that the user is in the °C MAX mode. 

L1, L2 LED:

 if on, the temperature of one PT sensor reached the corresponding L1 or L2 programmed threshold and the corresponding relay is active. 

FAN  LED:

  if  on, 

the  “always  ON”  mode  is  active  and  the  FAN  relay  will 

always  be  active.  If  flashing,  the  temperature  of  one  PT  sensor  reached  the 

corresponding FAN programmed threshold or the weekly fan activation function is active and the FAN relay is active. 

PT1, PT2, PT3, PT4 LEDs:

 if on, the temperature of one of the corresponding PT sensors reached the L1 or L2 programmed threshold and the corresponding 

relay is active. If flashing, the respective PT sensor is in fault. 

FAULT LED:

 if flashing, it indicates that the flashing PT1, PT2, PT3, PT4, is in fault. The fault cause will be showed through the °C display when positioned 

with the arrow buttons on the faulty sensor: Fcc in case of short circuit and Fco for open circuit. Dropout condition for Fcc: T 

≥ 

-7 °C. Dropout condition for 

Fco: 

T ≤ 23

9 °C.  

AUTO LED:

 if on, it means the user is in the AUTO SCAN mode. 

HMI Test:

 depending on which menu the user is in, by pressing the SET, °C MAX, AUTO button and then keeping the DOWN button pressed, all LEDs and 

seven segment LEDs will turn on. 

SCAN, AUTO SCAN:

 in AUTO SCAN mode, the device will automatically scan between each PT sensor temperature showing it on the display every 5sec 

allowing the user to see all the temperatures. To exit from the AUTO SCAN function, press any arrow button. The user will still be able to manually scan by 
using the UP/DOWN buttons. By pressing the SET, °C MAX, AUTO button until the AUTO LED turns on, the AUTO SCAN function will reactivate. To activate 
the AUTO SCAN function in °C MAX, select the °C MAX mode with the same button and keep the UP button pressed for more than 2sec. 

FAN:

 the FAN button 

allows to switch between “always ON” or Automatic Fan Operation. In “always ON” mode, the 

fan will always be ON and the FAN LED 

will be ON. In automatic mode, the fan will be ON and the FAN LED will blink when one PT sensor reaches the corresponding FAN programmed threshold. 
If the setpoint 

FAN ACTIVATION 

= OFF

, the manual fan will still allow the user to close/open the fan output contact.  

 
 
 
 

Отзывы: