TR-42 Temperature Protection Relay

 

4

 

Instruction Manual: TR42 GBM 25/02/2021

 

 

CALIBRATION CORRECTION AT 20mA 

(Optional: see 

ORDER CODE)

 

 

 

 

 

 

 

 

 

0.800÷1.200 

Step: 0.001

 

20mA will be applied to the output and it will be possible to correct 
the calibration value. 

FIRMWARE UPGRADE 

 

 

 

Note: 

for manufacturer’s use only.

 

 

 

8.

 

MAINTENANCE 

The device has been constructed principally with solid state technology, so it needs a simple maintenance. The operations of maintenance are simplified 
as follows: keep the relay dry and clean, verify that all terminal blocks are well connected, periodically check the display test by which all LEDs will be on, 
periodically control the right function of the output relays. 
 

9.

 

WARRANTY 

The purchased product is covered by the manufacturer's or seller's warranty within the terms set out in the General Conditions of Sale, which can be 
consulted on the website www.orionitalia.com and/or in the purchase contract stipulated. Orion Italia, S.r.l. warrants this product to be free from defects 
in material and workmanship. To exercise this warranty, write or call your local Orion Italia representative, or contact Orion Italia in Piacenza, Italy. You will 
be given prompt assistance. 
 

10.

 

ORDER CODE 

Model

 

Description

 

TR42CM 

Communication Port RS485 

TR42AD 

Communication Port RS485 + 4-20mA  Buzzer 

 

11.

 

SPECIFICATIONS 

Scale:

 -10 ÷ +240 °C 

Accuracy:

 ±1% F.S. ± 1 digit 

Settings:

 L1, L2, FAN: 0 ÷ 220 °C 

Supply voltage

: 24-240 Vcc/Vca (50-60Hz), -15%, +10% 

Maximum power consumption

: 4VA or 4W 

Inputs:

 4 platinum sensors PT100 with 3 wires. 500 Ohm max wire impedance. 

Outputs:

 FAN: normally open, Imax 16A 240Vac/24Vdc resistive load (7A 

continuous) /1HP 240 Vac.   L1,L2: change-over 5A(n.o) res. load 250 Vac. 
FAULT: 5A(n.c) 

Operational Temperature

:  0 ÷ 50 °C 

Storage Temperature

:  

20 ÷ 70 °C 

Relative Humidity

:  90% (non-condensing) 

Burn in:

 48 hours 

Dielectric Withstand Voltage:

 2 kVac, 60s 

Construction:

 according to the VDE, UL, CEI standards. 

Terminal block:

 draw-out terminals for 4 mm² cables (12 AWG). 

Frame

: In ABS self-extinguish with frontal protection (IP54). 

Assembly:

 to be fixed in the structure through stirrups and screws. 

Dimensions:

 96x96x114 mm 

Cutout:

 91-0,5x 91-0,5 mm (±0,5 mm)  

Weight: 

500 grams

 

Communication port:

 Insulated RS-485, insulation 1500 Vdc. 

Communication protocol:

 MODBUS RTU, function: 03h, 04h, 05h, 06h, 10h. 

4-20  mA  output: 

Internal  power  supply  15  Vdc,  max.  Voltage  drop  10  V, 

insulation  voltage  1500  Vdc.  Range:  0  °C÷240

 

°C.  Accuracy:  ±1%  F.S. 

No 

external power supply needed.

 

 

Emissions Tests:

 

Radiated emissions: EN 55011; Port: enclosure. 
Conducted emissions: EN 55011; Port: AC mains. 

 

 

Immunity Tests:

 

 

Conducted disturbances induced by RF field: EN 61000-4-6; Port: AC mains 
and signal lines. 

 

Radiated electromagnetic field: EN 61000-4-3; Port: enclosure. 

 

Electrostatic discharge: EN 61000-4-2; Port: enclosure. 

 

Fast transients (burst): EN 61000-4-4; Port: AC mains and signal lines. 

 

Surge: EN 61000-4-5; Port: AC mains. 

 

Voltage dips and short interruptions: EN 61000-4-11; Port: AC mains. 

 

  