TR-42 Temperature Protection Relay
4
Instruction Manual: TR42 GBM 25/02/2021
CALIBRATION CORRECTION AT 20mA
(Optional: see
ORDER CODE)
0.800÷1.200
Step: 0.001
20mA will be applied to the output and it will be possible to correct
the calibration value.
FIRMWARE UPGRADE
;
Note:
for manufacturer’s use only.
8.
MAINTENANCE
The device has been constructed principally with solid state technology, so it needs a simple maintenance. The operations of maintenance are simplified
as follows: keep the relay dry and clean, verify that all terminal blocks are well connected, periodically check the display test by which all LEDs will be on,
periodically control the right function of the output relays.
9.
WARRANTY
The purchased product is covered by the manufacturer's or seller's warranty within the terms set out in the General Conditions of Sale, which can be
consulted on the website www.orionitalia.com and/or in the purchase contract stipulated. Orion Italia, S.r.l. warrants this product to be free from defects
in material and workmanship. To exercise this warranty, write or call your local Orion Italia representative, or contact Orion Italia in Piacenza, Italy. You will
be given prompt assistance.
10.
ORDER CODE
Model
Description
TR42CM
Communication Port RS485
TR42AD
Communication Port RS485 + 4-20mA Buzzer
11.
SPECIFICATIONS
Scale:
-10 ÷ +240 °C
Accuracy:
±1% F.S. ± 1 digit
Settings:
L1, L2, FAN: 0 ÷ 220 °C
Supply voltage
: 24-240 Vcc/Vca (50-60Hz), -15%, +10%
Maximum power consumption
: 4VA or 4W
Inputs:
4 platinum sensors PT100 with 3 wires. 500 Ohm max wire impedance.
Outputs:
FAN: normally open, Imax 16A 240Vac/24Vdc resistive load (7A
continuous) /1HP 240 Vac. L1,L2: change-over 5A(n.o) res. load 250 Vac.
FAULT: 5A(n.c)
Operational Temperature
: 0 ÷ 50 °C
Storage Temperature
:
–
20 ÷ 70 °C
Relative Humidity
: 90% (non-condensing)
Burn in:
48 hours
Dielectric Withstand Voltage:
2 kVac, 60s
Construction:
according to the VDE, UL, CEI standards.
Terminal block:
draw-out terminals for 4 mm² cables (12 AWG).
Frame
: In ABS self-extinguish with frontal protection (IP54).
Assembly:
to be fixed in the structure through stirrups and screws.
Dimensions:
96x96x114 mm
Cutout:
91-0,5x 91-0,5 mm (±0,5 mm)
Weight:
500 grams
Communication port:
Insulated RS-485, insulation 1500 Vdc.
Communication protocol:
MODBUS RTU, function: 03h, 04h, 05h, 06h, 10h.
4-20 mA output:
Internal power supply 15 Vdc, max. Voltage drop 10 V,
insulation voltage 1500 Vdc. Range: 0 °C÷240
°C. Accuracy: ±1% F.S.
No
external power supply needed.
Emissions Tests:
Radiated emissions: EN 55011; Port: enclosure.
Conducted emissions: EN 55011; Port: AC mains.
Immunity Tests:
•
Conducted disturbances induced by RF field: EN 61000-4-6; Port: AC mains
and signal lines.
•
Radiated electromagnetic field: EN 61000-4-3; Port: enclosure.
•
Electrostatic discharge: EN 61000-4-2; Port: enclosure.
•
Fast transients (burst): EN 61000-4-4; Port: AC mains and signal lines.
•
Surge: EN 61000-4-5; Port: AC mains.
•
Voltage dips and short interruptions: EN 61000-4-11; Port: AC mains.