750/760 Feeder Management Relay
GE Power Management
7.5 LOGIC DIAGRAMS
7 SETPOINTS
7
7.5 LOGIC DIAGRAMS
7.5.1 DESCRIPTION
The logic diagrams provided should be referred to for a complete comprehensive understanding of the opera-
tion of each feature. These sequential logic diagrams illustrate how each setpoint, input parameter, and inter-
nal logic is used in a feature to obtain an output. In addition to these logic diagrams, written descriptions are
provided in the setpoints chapter which includes each feature.
7.5.2 SETPOINTS
•
Shown as a block with a shaded heading labeled ‘SETPOINT’.
•
The location of setpoints is indicated by the path heading on the diagram.
•
The exact wording of the displayed setpoint message identifies the setpoint.
•
Major functional setpoint selections are listed below the name and are incorporated in the logic.
7.5.3 MEASUREMENT UNITS
•
Shown as a block with an inset box labeled ‘RUN’.
•
The associated pickup or dropout setpoint is shown directly above.
•
Element operation of the detector is controlled by the signal entering the ‘RUN’ inset. The measurement /
comparison can only be performed if a logic ‘1’ is provided at the ‘RUN’ input.
•
Relationship between setpoint and input parameter is indicated by mathematical symbols:
‘<‘ (less than), ‘>‘ (greater than), etc.
•
ANSI device number (if one exists) is indicated above the block.
7.5.4 TIME DELAYS
•
Shown as a block with the following schematic symbol,
————
.
•
If delay is adjustable, associated delay setpoint is shown directly above, and schematic symbol has an
additional variability indication, an oblique bar.
•
ANSI device number (62) is indicated above the block.
7.5.5 LED INDICATORS
•
Shown as the following schematic symbol,
⊗.
•
The exact wording of the front panel label identifies the indicator.
7.5.6 LOGIC
•
Described using basic logic gates ( ‘AND’, ‘OR’, ‘XOR’, ‘NAND’, ‘NOR’, ... )
•
The inverter symbol, a logical NOT, is shown as a circle,
.
7.5.7 CONDITIONS
•
Shown as a rounded block with a shaded heading labeled ‘CONDITION’.
•
Conditions are mutually exclusive, i.e., only one condition can be active at any point in time.
•
Conditions latch until another condition becomes active.
•
The output of an active condition is 1 or logic high.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...