GE Power Management
750/760 Feeder Management Relay
16-
51
16 COMMUNICATIONS
16.4 MODBUS MEMORY MAP
16
1953
3
Fault Sensitive Ground Current Position
0 to 359
° Lag
F1
0°
S8
SIMULATION POST-FAULT VALUES
READ/WRITE
1960
Postfault Bus Voltage Level
0.00 to 2.00
x VT
F3
1.00 x VT
1961
Postfault Bus Voltage Frequency
20.00 to 65.00
Hz
F3
60.00 Hz
1962
Postfault Synchronous Voltage Level
0.00 to 2.00
x VT
F3
1.00 x VT
1963
Postfault Synchronous Voltage Position
0 to 359
° Lag
F1
0°
1964
Postfault Synchronous Voltage Frequency
20.00 to 65.00
Hz
F3
60.00 Hz
S5
BREAKER FAILURE
READ/WRITE
1980
Breaker Failure Function
---
---
F38
Disabled
1981
Breaker Failure Relays
---
---
F57
None
1982
Breaker Failure Delay 1
0.03 to 1.00
s
F3
0.10 s
1983
Breaker Failure Current
0.05 to 20.00
x CT
F3
1.00 x CT
1984
Breaker Failure Delay 2
0.00 to 1.00
s
F3
0.00 s
S6
BREAKER OPERATION
READ/WRITE
1988
Breaker Operation Function
---
---
F38
Disabled
1989
Breaker Operation Relays
---
---
F57
None
198A
Breaker Operation Delay
0.03 to 1.00
s
F3
0.10 s
S6
COIL MONITOR 1
READ/WRITE
1990
Coil Monitor 1 Function
---
---
F38
Disabled
1991
Coil Monitor 1 Relays
---
---
F57
None
1992
Breaker State Bypass
---
---
F30
Disabled
1993
8
Coil Monitor 1 Delay
5 to 100
s
F1
5 s
1994
8
Coil Monitor 1 Type
---
---
F90
Trip
S6
COIL MONITOR 2
READ/WRITE
1998
Coil Monitor 2 Function
---
---
F38
Disabled
1999
Coil Monitor 2 Relays
---
---
F57
None
199A
Breaker State Bypass
---
---
F30
Disabled
199B
8
Coil Monitor 2 Delay
5 to 100
s
F1
5 s
199C
8
Coil Monitor 2 Type
---
---
F90
Close
S6
8
COIL MONITOR NAMES
READ/WRITE
19A0
8
Coil Monitor 1 Name (9 registers)
---
---
F33
Trip Coil Monitor
19A9
8
Coil Monitor 2 Name (9 registers)
---
---
F33
C lo se C oil M onitor
S6
8
ANALOG INPUT THRESHOLD NAMES
READ/WRITE
19B2
8
Analog Input Threshold 1 Name (9 registers)
---
---
F33
Analog Threshld 1
19BB
8
Analog Input Threshold 2 Name (9 registers)
---
---
F33
A n a lo g T h reshld 2
Table 16–15: MODBUS MEMORY MAP (Sheet 34 of 41)
ADDR
DESCRIPTION
RANGE
UNITS
TYPE
FACTORY
DEFAULT
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–59.
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...