![GE 750 Скачать руководство пользователя страница 417](http://html.mh-extra.com/html/ge/750/750_instruction-manual_131794417.webp)
GE Power Management
750/760 Feeder Management Relay
17-
11
17 COMMISSIONING
17.5 OUTPUT RELAYS
17
17.5 OUTPUT RELAYS
17.5.1 INDICATORS
Front panel OUTPUT STATUS indicators.
17.5.2 PROCEDURE
1.
Enter settings under subheading
S8 TESTING \ OUTPUT RELAYS \
FORCE OUTPUT RELAYS FUNCTION:
Enabled
FORCE 1 TRIP RELAY:
De-energized
FORCE 2 CLOSE RELAY:
De-energized
FORCE 3 AUXILIARY RELAY:
De-energized
FORCE 4 AUXILIARY RELAY:
De-energized
FORCE 5 AUXILIARY RELAY:
De-energized
FORCE 6 AUXILIARY RELAY:
De-energized
FORCE 7 AUXILIARY RELAY:
De-energized
FORCE 8 SELF-TEST RELAY:
De-energized
FORCE SOLID STATE OUTPUT:
De-energized
2.
Using a multimeter, check that all output relays are de-energized (i.e. N.O. contacts are open, N.C. con-
tacts are closed).
3.
Change setting to:
S8 TESTING \ OUTPUT RELAYS \ FORCE 1 TRIP RELAY
:
Energized
4.
Check that the 1 TRIP output is energized (i.e. N.O. contacts are closed), and the 1 TRIP indicator on the
faceplate is illuminated.
5.
Change setting to:
S8 TESTING \ OUTPUT RELAYS \ FORCE 1 TRIP RELAY
:
De-Energized
6.
Repeat steps 3 through 5 for output relays 2 through 8 inclusive.
7.
Observing polarity, connect a DC source of a minimum of 5 volt, in series with a limiting resistor that will
permit a minimum current of 100 mA, in series with the Solid State output. Observing polarity, connect a
DC voltmeter across the limiting resistor. Check there is no voltage displayed on the voltmeter.
8.
Change setting to:
S8 TESTING \ OUTPUT RELAYS \ FORCE SOLID STATE OUTPUT
:
Energized
9.
Check that a voltage has appeared on the voltmeter. Turn off the source and disconnect the test wiring.
10. Change setting to:
S8 TESTING \ OUTPUT RELAYS \ FORCE SOLID STATE OUTPUT
:
De-Energized
11. Change setting to:
S8 TESTING \ OUTPUT RELAYS \ FORCE OUTPUT RELAYS FUNCTION
:
Disabled
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...