3.2 TYPICAL WIRING
3 INSTALLATION
3
3.2.7 RESTRICTED EARTH FAULT INPUTS
Restricted Earth Fault protection is often applied to transformers having grounded wye windings to provide
sensitive ground fault detection for faults near the transformer neutral. The Sensitive Ground input (terminals
G3, H3) can be used.
Although the 750/760 is designed for feeder protection, it can provide Restricted Earth Fault protec-
tion on transformers that do not have dedicated protection. To use the 750/760 for this type of protec-
tion, a stabilizing resistor and possibly a non-linear resistor will be required. For more details see
Section 12.5.6: RESTRICTED EARTH FAULT on page 12–37.
Figure 3–12: RESTRICTED EARTH FAULT INPUTS
NOTE
Содержание 750
Страница 2: ......
Страница 4: ......
Страница 124: ...8 14 750 760 Feeder Management Relay GE Power Management 8 12 INSTALLATION 8 S1 RELAY SETUP 8 ...
Страница 144: ...10 14 750 760 Feeder Management Relay GE Power Management 10 10 MISCELLANEOUS FUNCTIONS 10 S3 LOGIC INPUTS 10 ...
Страница 152: ...11 8 750 760 Feeder Management Relay GE Power Management 11 3 OUTPUT RELAYS 3 7 AUXILIARY 11 S4 OUTPUT RELAYS 11 ...
Страница 216: ...12 64 750 760 Feeder Management Relay GE Power Management 12 9 BREAKER FAILURE 12 S5 PROTECTION 12 ...
Страница 484: ...17 78 750 760 Feeder Management Relay GE Power Management 17 10 PLACING THE RELAY IN SERVICE 17 COMMISSIONING 17 ...
Страница 488: ...A 4 750 760 Feeder Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Страница 490: ...B 2 750 760 Feeder Management Relay GE Power Management B 1 EU DECLARATION OF CONFORMITY APPENDIXB B ...
Страница 492: ...C 2 750 760 Feeder Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Страница 502: ...x 750 760 Feeder Management Relay GE Power Management INDEX ...
Страница 503: ...GE Power Management 750 760 Feeder Management Relay NOTES ...