Primis Relay Bridge
™
Elevator Control
Installation Guide
PART NUMBERS
FR-50-40-E, FR-50-40-EL
FR-50-24-E
PHYSICAL SPECIFICATIONS
Length
277 mm (10.91 in.)
Width
165 mm (6.50 in.)
Height
24 mm (0.94 in.)
Weight
564 g (19.89 oz.)
Max Readers
2
(each reader requires a FR-50-40-W485 adapter)
Max Input
0
Max Output
24
Electrical:
UL294 and UL294B
EMI Radiation:
FCC Part 15 Class B
SUMMARIZED LEVELS OF
ACCESS CONTROL COMPONENTS
Destructive Attack
Level I
Line Security
Level I
Endurance
Level I
Standby Power
Level I
Single Point Locking
Level I
The RS-485 input on the FR-50-40-E is intended for use in elevator cabs.
Two wire shielded cable running inside the travelling cable to the
elevator cab is connected to the RS-485 inputs on the FR-50-40-E Primis
Bridge and then connected to a FR-50-40-W485 (Wiegand to 485
adapter) in the cab.
A Wiegand output reader can then be connected to the inputs on the
FR-50-40-W485 adapter. Up to two reader adapters can be connected to
the RS-485 inputs on the FR-50-40-E.
The shield wire should only be connected at the RS-485 input on
the FR-50-40-E.
READER INSTALLATION REQUIREMENTS
Primis Bridges should only be installed in dry, non-condensing
environments. The ambient temperature of the environment should
range between -40°C and 50°C.
Primis Encryption Bridges should only be mounted to non-conductive
surfaces. Incorrect mounting may short-circuit the electronics, which will
cause it to malfunction.
INSTALLATION REQUIREMENTS
1.
Wire any output devices to the Relay Outputs shown on the wiring
reference on the back.
2.
Supply power to the Primis Bridge using 12 - 16 Vdc & 1500
mA (1500 mA internal; ~60.4 mA per relay) DC power connected
directly to the Power In terminal on the Primis Bridge.
3.
Connect a Cat5e or Cat6 cable from any port on an Ethernet
switch to the RJ-45 connector on the Primis Bridge. Ensure
that the length of the cable between the switch to the Primis
Bridge is 100m or less. Greater lengths can be achieved by adding
switches or repeaters every 100m.
4.
INSTALLATION PROCEDURE
the Primis Bridge circuit board indicates
that the bridge is powered but not
connected to a server.
A solid green “Ready” LED light indicates
that the Primis Bridge has established a
connection to the server and is ready to use.
To configure and add the Primis Bridge to a MESH/Primis
Server, refer to the MESH/Primis Solution Guide manual. the
RJ-45 connector on the Primis Bridge.
Note
: Ethernet only
supports a maximum cable length of 100 m.
DC power, reader, and output device wires should be between 16-28
AWG. They should also be stripped 5.5mm to sufficiently fit the terminal
blocks and ensure that they do not come in contact with each other.