Emergency Stop Safety Relay ESM-BA2.. 

V1.1.0 

• 

Cyclical monitoring of the output contacts 

• 

Indication of the switching state via LED 

• 

2 start behaviors possible: 

   - Monitored manual start 

   -  Automatic start 

• 

Up to PL e, SILCL 3, category 4 

Correct Use 

The  ESM-BA2..  is  a  universal  emergency  stop  safety  switching 
device  with  two  safe  relay  outputs  that  can  quickly  and  safely 
stop the moving parts of a machine or system in case of danger.  

Applications  for  the  ESM-BA2..  include  single  or  dual-channel 
emergency stop circuits and guard monitoring on machines and 
systems. 

Features 

• 

2 safe, redundant relay outputs 

• 

Connection of: 

    -  Emergency stop buttons 
    -  Safety switches 
    -  Non-contact safety switches 

    -  OSSD-Outputs 

• 

Single and dual-channel operation possible 

• 

Feedback loop for monitoring downstream contactors or 
expansion modules 

Function 

The emergency stop safety switching device ESM-BA2.. is 
designed  for  safe  isolation  of  safety  circuits  according  to 
DIN EN 60204-1 and can be used up to safety category 4, 
PL e according to DIN EN ISO 13849-1. 

The internal logical system closes the safety contacts when 
the start button is pressed. 

When  the  emergency  stop  circuit  is  opened,  the  positively 
driven  safety  contacts  are  opened  and  safely  switch  the 
machine  off.  It  is  ensured  that  a  single  fault  does  not  lead 
to a loss of the safety function and that every fault is detec-
ted  by  cyclical  self-monitoring  no  later  than  when  the  sys-
tem is switched off and switched on again. 

Electrical  
Connection 

• 

When the 24 V  version is used, a safety transformer 
according to EN 61558-2-6 or a power supply unit with 
electrical isolation from the mains must be connected. 

• 

External fusing of the safety contacts must be provided. 

• 

A maximum length of the control lines of 1000 meters 
with a line cross section of 0.75 mm

2

 must not be excee-

ded. 

• 

The line cross section must not exceed 2.5 mm

2

• 

If the device does not function after commissioning, it 
must be returned to the manufacturer unopened. Ope-
ning the device will void the warranty. 

Installation 

As per DIN EN 60204-1, the device is intended for installa-
tion in control cabinets with a minimum degree of protection 
of  IP54.  It  is  mounted  on  a  35-mm  DIN  rail  according  to 
DIN EN 60715 TH35. 

Safety Precautions 

Fig. 1 Block diagram ESM-BA2.. 

Fig. 2 Installation / removal 

Fig. 3 Connections 

A1: 

 Power supply 

A2. 

 Power supply 

S11:  

DC 24 V control voltage 

S10:  

Control line 

S21:  

Start control line 

S13:  

Control line 

S14:  

Control line 

S12:  

Control line 

13-14:  

Safety contact 1 

23-24:  

Safety contact 2 

 

• 

All relevant safety regulations and standards are to be 
observed. 

• 

The overall concept of the control system in which the 
device is incorporated must be validated by the user. 

• 

Failure to observe the safety regulations can result in 
death, serious injury and serious damage. 

• 

Note down the version of the product (see label “Vx.x.x”) 
and check it prior to every commissioning of a new de-
vice. If the version has changed, the overall concept of 
the control system in which the device is incorporated 
must be validated again by the user. 

• 

Installation and commissioning of the device must be 
performed 

only by authorized personnel

• 

Observe the country-specific regulations when installing 
the device. 

• 

The electrical connection of the device is only allowed to 
be made with the device isolated. 

• 

The wiring of the device must comply with the instruc-
tions in this user information, otherwise there is a risk 
that the safety function will be lost. 

• 

It is not allowed to open the device, tamper with the 
device or bypass the safety devices. 

Содержание ESM-BA2 Series

Страница 1: ...ith electrical isolation from the mains must be connected External fusing of the safety contacts must be provided A maximum length of the control lines of 1000 meters with a line cross section of 0 75 mm2 must not be excee ded The line cross section must not exceed 2 5 mm2 If the device does not function after commissioning it must be returned to the manufacturer unopened Ope ning the device will ...

Страница 2: ...et close the start button to close the safety contacts Fig 6 Monitored manual start It is monitored that the start button was opened before the emergency stop button closes Prerequisite operating voltage must not be interrupted Fig 7 Automatic start Max perm delay during closing of the safety switches on S12 and S13 S12 before S13 300 ms S13 before S12 any Warning Safety contacts switch immediatel...

Страница 3: ...on 2 DIN VDE 0110 1 Overvoltage category 3 DIN VDE 0110 1 Weight approx 230 g Mounting DIN rail according to EN 60715 TH35 Note Additional data can be requested from the manufacturer for applications that deviate from these conditions Safety Characteristics According to EN ISO 13849 1 The device is certified according to EN ISO 13849 1 up to a Performance Level of PL e Device cannot be switched on...

Страница 4: ...75 33 16 www euchner de info euchner de Emergency Stop Safety Relay ESM BA2 V1 1 0 Dimension Drawing Subject to technical modifications no responsibility is accepted for the accuracy of this information EUCHNER GmbH Co KG 090071 06 02 16 Translation of the Original Operating Instructions Fixed Terminals Plug In Terminals ...

Отзывы: