manualshive.com logo in svg
background image

Cutler-Hammer 

I.L.  29-8858 

Instructions for  Digitrip  RMS  510  Trip  Unit 

Table of Contents 

Page 

1.0 

General Description 

..................... 1 

1.1 

Protection 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 

1.2 

Information 

............................ 2 

1.3 

Testing 

............................... 4 

2.0 

UL Listed Devices 

....................... 4 

3.0 

Principle of  Operation 

.................... 4 

3.1 

General 

............................... 4 

3.2 

Trip and Operation  Indicators 

.............. 5 

3.3 

Test Provisions 

......................... 5 

3.4 

DIScriminator (Making Current Release) 

..... 5 

3.5 

OVERRIDE (Fixed  Instantaneous) 

.......... 6 

3.6 

Zone  Interlocking 

........................ 6 

4.0 

Protection Settings 

...................... 6 

4.1 

General 

............................... 6 

4.2 

Long Delay Current Settings 

............... 7 

4.3 

Long Delay Time Settings 

................. 7 

4.4 

Short Delay  Current  Settings 

.............. 

4.5 

Short Delay Time Settings 

................ 

4.6 

Instantaneous Current Settings 

............. 

4.7 

NO  Instantaneous  Current Settings 

......... 

4.8 

Ground Fault Current Settings 

............. 

4.9 

Ground Fault Time Delay Settings 

.......... 9 

5.0 

Test Procedure 

........................ 10 

5.1 

General 

.............................. 10 

5.2 

When To Test 

......................... 11 

5.3 

Test Provision 

......................... 11 

5.4 

Conducting Tests 

...................... 11 

5.4.1 

Control Power 

......................... 11 

5.4.2 

Not Tripping the Breaker 

................. 12 

5.4.3 

Tripping the  Breaker 

.................... 12 

6.0 

Battery  (I nside the Rating Plug) 

........... 12 

6.1 

General 

.............................. 12 

6.2 

Battery  Check 

......................... 12 

6.3 

Battery  Replacement. 

................... 12 

7.0 

Auxiliary Power Module 

.................. 14 

8.0 

Frame Ratings,  (where applicable, 

Sensor Ratings)  and Rating Plugs 

........ 14 

9.0 

References 

........................... 15 

9.1 

Digitrip RMS Trip Assemblies 

............. 15 

9.2 

Type DS Low Voltage AC Power Circuit 

Breakers 

........................... 15 

9.3 

Type SPB Systems Pow-R Breakers 

....... 15 

9.4 

Series C%® R-Frame Molded Case Circuit 

Breakers 

........................... 15 

Appendix A Zone  Interlocking - Example 

........... 15 

Effective  May  1997,  Supersedes  I.L. 29-885A dated Septem-

WARNING 

DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN­
TENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. 
DEATH OR SEVERE PERSONAL INJURY CAN 
RESULT FROM CONTACT WITH ENERGIZED EQUIP­
MENT. ALWAYS VERIFY THAT NO VOLTAGE IS 
PRESENT BEFORE PROCEEDING  WITH THE TASK, 
AND ALWAYS FOLLOW GENERALLY ACCEPTED 
SAFETY PROCEDURES. CUTLER-HAMMER IS NOT 
LIABLE FOR THE MISAPPLICATION OR MISINSTAL­
LATION OF ITS PRODUCTS. 

It is strongly urged that the user observe all recommen­

dations,  warnings and cautions relating to the safety of 
personnel and equipment,  as well as general and local 
health and safety laws,  codes,  and procedures. 

The recommendations and information contained herein 
are based on experience and judgment,  but should not 
be considered to be all-inclusive or covering every appli­
cation or circumstance which may arise.  If you have any 

questions or need further information or instructions, 

please contact your local representative,  or the Customer 
Support Center for the type of circuit breaker you have: 

Circuit 

Call 

Send  to 

Breaker 

Telephone 

FAX 

Type 

Number 

Number 

DS/DSL 

(412)  937-6029 

(412)  937-6396 

SPB 

(412)  937-6029 

(412)  937-6396 

Series  C®  R-Frame 

(412) 937-6490 

(412)  937-6010 

1 .0  GENERAL DESCRIPTION 

1 .1  Protection 

The Digitrip RMS 

5 10, 

illustrated in Fig. 

1, 

is a custom 

application specific integrated circuit based trip unit suit­
able for use in types DS and DSL low voltage AC power 
circuit breakers and type SPB Systems Pow-R circuit 
breakers and Series C® R-Frame molded case circuit 
breakers. 

The Digitrip RMS 

5 10 

provides true RMS current sensing 

for proper correlation with thermal characteristics of con­
ductors and equipment. Interchangeable rating plugs are 
provided to establish the continuous current rating of 
each circuit breaker. 

www 

. ElectricalPartManuals 

. com

Содержание Digitrip RMS 510 LI

Страница 1: ...IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCE...

Страница 2: ...S Digitrip Type LI LS and LSI trip units can be applied on 3 pole or 4 pole circuit breakers for protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PRO TECTION Re...

Страница 3: ...rotection U Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection UG w w w E...

Страница 4: ...me Instantaneous Ground Protection LS G The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 I...

Страница 5: ...through the circuit breaker exceeds approximately 10 of the frame current sensor rating the green LED will flash On and Off once each second to indicate the trip unit is energized and operating prope...

Страница 6: ...tream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 885...

Страница 7: ...the breaker to trip in a time progressively earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 1 0 minutes it has reset fully so...

Страница 8: ...ght 8 times Ir the Long Delay Setting For currents greater than 8 times Ir the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Set...

Страница 9: ...60 200 240 300 400 UJ 0 600 150 180 210 240 300 360 450 600 UJ a 630 158 189 221 252 315 378 473 630 2 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 400 500 600 750 1000 J 1200 300 360 420 48...

Страница 10: ...it Required following all automatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip...

Страница 11: ...0 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indi cating that there is enough cu...

Страница 12: ...g make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting fr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current excee...

Страница 13: ...attery should be the same type or equivalent Acceptable 3 0 volt lithium batteries may be Fig 6 Typical Rating Plug Trip Unit Connector F u InII Keyed Cavity Page 13 obtained from the following compan...

Страница 14: ...t breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity t...

Страница 15: ...er APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used Fault 3 The br...

Страница 16: ...D any Zone Interlock Wiring The maximum distance between first and last zone is 250 feet 1 1 0 m A Maximum of 20 breakers may be con nected in parallel in one Zone F22 C SO SI 0 1 Sec Legend C Common...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 20: ...SE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer...

Отзывы: