manualshive.com logo in svg
background image

I.L.  29-8858 

Page 5 

(LiNE/UPPEI'I) 

r--------------------------------- -------------------

A

B

C

 

1  1  1 

, .  

A:i�:��;���) 

Input 

Protection 

Function s..tting 

By  SwItches and  PushbunoRR 

SeeSaction4. 

:urrent 

» 

_____ 

-.l 

""�" 

See Section 

8. 

CT's 

I  LOADI LOWER  I 

TypicllPhIIM 

r:=� 

Brid!!.", 
Circulta 

Internal 
...... 

SupplV 

II  Lighted 

RED, 

Indicat8sCeuee 
OfTRIP(Locatod 
On  Front  Panel! 

See Section 

1.2. 

I ntegrated  Circuit 

SJ.LRE+ 

TM 

Chip 

Fig. 3 

Digitrip RMS 510 Block Diagram with Breaker  Interface 

The microcomputer,  in cyclic fashion,  repeatedly scans 
the voltage values across each calibrating resistor and 
enters these values into its Random Access Memory 

(RAM). These data are used to calculate true RMS cur­

rent values,  which are then repeatedly compared with the 
protection function settings and other operating data 
stored in the Read Only Memory (ROM). The software 
program then determines whether to initiate protection 
functions,  including tripping the breaker through the low 
energy trip device (Flux Transfer Shunt Trip or Direct Trip 
Actuator)  in the circuit breaker. 

3.2  Trip and Operation Indicators 

The LEOs,  shown in Figs. 1 and 2.1-2.6,  on the face of 
the trip unit,  light "RED" to indicate the reason for any 

automatic trip operation. As indicated in Figs. 2.1-2.6, 
each LED is strategically located in the related segment 
of the time-current curve depicted on the face of the trip 

unit. The reason for trip is identified by the segment of the 
time-current curve where the LED is lighted "RED". Fol­
lowing an automatic trip operation,  the back-up battery, 
continues to supply power to the LEOs as indicated in 
Figs. 

and 6. To check the status of the battery,  see 

Section 6. 

Push the "Trip Reset" button shown in Fig. 1,  to turn "Off' 
the LEOs following a trip operation. 

A green colored LED,  as shown in Fig. 1,  indicates the 
operational status of the trip unit. Once the load current 
through the circuit breaker exceeds approximately 10% 
of the frame/current sensor rating,  the green LED will 
flash "On" and "Off' once each second, to indicate the trip 
unit is energized and operating properly. 

Note:  If the LED is steadily  "GREEN",  i.e. not flash­
ing,  the trip unit is not ready. 

Effective  May  1997 

3.3 Test Provisions (See Section 5.0) 

3.4 DIScriminator (Making Current Release) 

(For Types LS and 

LSG 

trip units only.) 

When the Digitrip RMS 510 Trip Unit is not equipped with 
an adjustable instantaneous protection setting,  i.e.,  types 
LS or LSG,  a making current release  (or DIScriminator) 
circuit is provided. This circuit will prevent the circuit 
breaker from being closed and latched-in on a faulted cir­
cuit. The non-adjustable release is pre-set at eleven (11) 
times the installed rating plug current (In). 

The making current release is enabled only for the first 
ten  (10) cycles following an initial circuit breaker closing 
operation,  provided the load current exceeds approxi­
mately 10% of the ci rcu it breaker frame (or cu rrent sen­
sor) rating. Should the load current through the circuit 
breaker drop to less than the 10% value,  the release will 
reset. The release,  once reset,  will remain enabled until 
the load current passing through the circuit breaker has 
exceeded the 10% value for 10 cycles. The making cur­
rent release will trip the circuit breaker instantaneously. 

In the event the breaker is intended to close  (but not to 

trip out again) into a circuit whose current could initially 
be higher than 11 x In,  it is possible to make the DIScrim­
inator inactive. If the breaker does close onto a fully rated 
fault current,  when the DIScriminator is inactive,  the 
breaker will wait for the full short-time delay setting 
before it trips. The DIScriminator (making current 
release)  can be made 

inactive 

by turning the 

"OVER­

RIDE/" 

setting switch (nearest the bottom edge of the trip 

unit)  from the "DIS"  position,  to the 

"[BLANK]" 

position. 

(See Figs. 2.2 and 2.5.) 

www 

. ElectricalPartManuals 

. com

Содержание Digitrip RMS 510 LI

Страница 1: ...IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCE...

Страница 2: ...S Digitrip Type LI LS and LSI trip units can be applied on 3 pole or 4 pole circuit breakers for protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PRO TECTION Re...

Страница 3: ...rotection U Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection UG w w w E...

Страница 4: ...me Instantaneous Ground Protection LS G The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 I...

Страница 5: ...through the circuit breaker exceeds approximately 10 of the frame current sensor rating the green LED will flash On and Off once each second to indicate the trip unit is energized and operating prope...

Страница 6: ...tream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 885...

Страница 7: ...the breaker to trip in a time progressively earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 1 0 minutes it has reset fully so...

Страница 8: ...ght 8 times Ir the Long Delay Setting For currents greater than 8 times Ir the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Set...

Страница 9: ...60 200 240 300 400 UJ 0 600 150 180 210 240 300 360 450 600 UJ a 630 158 189 221 252 315 378 473 630 2 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 400 500 600 750 1000 J 1200 300 360 420 48...

Страница 10: ...it Required following all automatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip...

Страница 11: ...0 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indi cating that there is enough cu...

Страница 12: ...g make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting fr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current excee...

Страница 13: ...attery should be the same type or equivalent Acceptable 3 0 volt lithium batteries may be Fig 6 Typical Rating Plug Trip Unit Connector F u InII Keyed Cavity Page 13 obtained from the following compan...

Страница 14: ...t breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity t...

Страница 15: ...er APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used Fault 3 The br...

Страница 16: ...D any Zone Interlock Wiring The maximum distance between first and last zone is 250 feet 1 1 0 m A Maximum of 20 breakers may be con nected in parallel in one Zone F22 C SO SI 0 1 Sec Legend C Common...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 20: ...SE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer...

Отзывы: