manualshive.com logo in svg
background image

Page  10 

\ \ 

Gnd  Fault 

Time 

III 

Sec. 

"'""' 

I  I 

I  I 

Available 

Settings 

.1 

• .  

• .  

• .  

• .  

l- -

-

Seconds  with 

- - _I 

Flat  Response 

1\... 

__  _ 

____ 

�S�� 

Returns  to 

Flat 

� 

Response  at 

� 

Approximatelv 

II', 

___ 

.... , ....  I 

.1*,  .3*,  .5* 

.... .... 

'" 

Seconds  with 

� 

__ 

0.625  In 

"."In  Viewing  Window  '  ............  I 

1"1 

Shape 

Indicates 

..............  -

J2t  Shape 

'- - __ 

Fig. 4.7 

Ground Fault  Time Delay Settings 

Note:  See also Section 3.6 on Zone Interlocking. 

5.0 TEST PROCEDURES 

5.1  General 

DANGER 

DO NOT ATTEMPT TO INSTALL, TEST OR PERFORM 
MAINTENANCE ON EQUIPMENT WHILE IT IS ENER­
GIZED. DEATH OR SEVERE PERSONAL INJURY 
CAN RESULT FROM CONTACT WITH ENERGIZED 
EQUIPMENT. 

DE-ENERGIZE THE CIRCUIT AND DISCONNECT THE 
CIRCUIT BREAKER BEFORE PERFORMING  MAINTE­
NANCE OR TESTS. 

As illustrated in Figs. 1 and 5,  an integral test panel is 

provided to test the Digitrip  RMS 510  Trip  Unit. 

Several no-trip settings are provided to check the trip unit 
operation without actually tripping the circuit breaker. 

Breaker  Trips 

At 

6T 

and 

GFT 

Test  Amps 

[ill<D 

x  In 

Test 

®  0 

Trip 

®  0 

Reset 

U

n

i

Status 

I.L.  29-8858 

Available  "Test  Amps"  Settings 

<D 

"6T" = Phase  Current  Test  at 

6xln 

and 

TRIPS  breaker; 

"1.2.3.8 

or 

10" 

=Phase 

Current  Test - NO

!J:,

reaker 

TRIP; 

"GFT" 

=Ground 

Current 

Test 

and 

TRIPS  breaker; 

"GF" 

Ground 

C

u

r

r

e

n

t  Test 

-

NO 

breaker 

TRIP. 

See  Section 

5.4.3 

for  inser­

vice  test  trip  limitations. 

® 

Push.  then  release Trip  Reset 
button  to  reset  Trip  Unit. 
Required  following  all 

automatic  trip  and  test 
operations. 

® 

Push.  then  release  Test 

button  to  test.  Test  operation 
begins with  release  of 
pushbutton. 

Fig. 5 

Integral  Test Panel (Lower Right Corner of Trip 

Unit) 

CAUTION 

TESTING  A CIRCUIT BREAKER UNDER "TRIP CON­
DITIONS" WHILE IT IS IN SERVICE AND CARRYING 
LOAD CURRENT,  WHETHER DONE BY INTERNAL 
OR EXTERNAL MEANS,  IS NOT RECOMMENDED. 

ANY TRIPPING  OPERATION WILL CAUSE DISRUP­
TION OF SERVICE AND POSSIBLE PERSONAL 
INJURY RESULTING  FROM UNNECESSARY 
SWITCHING  OF CONNECTED EQUIPMENT. 

TESTING  OF A CIRCUIT BREAKER THAT RESULTS 
IN THE TRIPPING  OF THE CIRCUIT BREAKER 
SHOULD BE DONE ONLY WITH THE CIRCUIT 
BREAKER IN THE "TEST" OR "DISCONNECTED" 
CELL POSITIONS OR WHILE THE CIRCUIT 
BREAKER IS ON A TEST BENCH. 

To preserve the primary protection function of the trip 
unit,  all in-service testing under "Trip" or "No-Trip" condi­
tions are only performed at load current values no greater 
than 50%  of the Long Delay Current Setting, 

Ir' 

Any 

attempt to conduct in-service testing when the load cur­
rent exceeds 50%  of 

Ir' 

will not be executed by the trip 

unit. 

Since the Digitrip RMS 510 Trip  Unit is completely self­
powered using energy derived from the current sensors 
installed in the circuit breaker,  all in-service tests con­
ducted should be conducted with the auxiliary control 
power module,  shown in Fig. 7,  plugged into the trip unit. 
This action will avoid difficulties caused by load current 
levels that are too low to operate the trip unit. 

Effective May  1997 

www 

. ElectricalPartManuals 

. com

Содержание Digitrip RMS 510 LI

Страница 1: ...IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCE...

Страница 2: ...S Digitrip Type LI LS and LSI trip units can be applied on 3 pole or 4 pole circuit breakers for protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PRO TECTION Re...

Страница 3: ...rotection U Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection UG w w w E...

Страница 4: ...me Instantaneous Ground Protection LS G The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 I...

Страница 5: ...through the circuit breaker exceeds approximately 10 of the frame current sensor rating the green LED will flash On and Off once each second to indicate the trip unit is energized and operating prope...

Страница 6: ...tream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 885...

Страница 7: ...the breaker to trip in a time progressively earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 1 0 minutes it has reset fully so...

Страница 8: ...ght 8 times Ir the Long Delay Setting For currents greater than 8 times Ir the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Set...

Страница 9: ...60 200 240 300 400 UJ 0 600 150 180 210 240 300 360 450 600 UJ a 630 158 189 221 252 315 378 473 630 2 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 400 500 600 750 1000 J 1200 300 360 420 48...

Страница 10: ...it Required following all automatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip...

Страница 11: ...0 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indi cating that there is enough cu...

Страница 12: ...g make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting fr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current excee...

Страница 13: ...attery should be the same type or equivalent Acceptable 3 0 volt lithium batteries may be Fig 6 Typical Rating Plug Trip Unit Connector F u InII Keyed Cavity Page 13 obtained from the following compan...

Страница 14: ...t breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity t...

Страница 15: ...er APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used Fault 3 The br...

Страница 16: ...D any Zone Interlock Wiring The maximum distance between first and last zone is 250 feet 1 1 0 m A Maximum of 20 breakers may be con nected in parallel in one Zone F22 C SO SI 0 1 Sec Legend C Common...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 20: ...SE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer...

Отзывы: