background image

114

99

99

35

35

114

45

45

Part Numbers    

Part Numbers

Terminal Style

HR1S-ATE5110

Integrated Terminal Block

HR1S-ATE5110P

Removable Terminal Block

Dimensions (mm)

LED Indicator

Specifications

Applicable Standards

EN 60204-1: 2007, EN 60947-1: 2007

EN 60947-5-1:2004, EN 61000-6-2: 2005

EN 61000-6-4: 2007, EN 62061: 2005

EN ISO 13849-1: 2008, EN ISO 13849-2: 2008

Applicable Standards 

for Use

EN 60204-1: 2006

EN ISO 13850: 2008

Performance Level (PL)

e (EN ISO 13849-1)

Safety Category

4 (EN ISO 13849-1)

Safety Integrity Level (SIL)

3 (EN 62061)

Stop Category

0, 1 (EN 60204-1) (Note)

Operating Temperature

–10 to +55ºC  (no freezing)

Relative Humidity

30 to 85% RH (no condensation)

Impulse Withstand Voltage

4 kV (IEC 60947-5-1)

Shock Resistance

150 m/s2, 11m sec, 3 shocks in each 3 axes

Vibration Resistance

10 to 60 Hz, amplitude 0.35 mm

60 to 150 Hz, acceleration 50 m/s2

Degree of Protection

Terminal: IP20   Enclosure: IP40

Rated Voltage

24V AC –20% +10%

24V DC –20% +20%

Power Consumption

24V AC: 8 VA max. 24V DC: 4W max.

Overcurrent Protection

Built-in, electronic

Minimal Applicable Load

17V DC / 10 mA (initial value)

Response Time

ON to OFF: 20 ms max. (instantaneous output)

Overvoltage Category

III

Pollution Degree

2

Rated Insulation Voltage

300V AC

Safety  Outputs

Instantaneous (Stop Cat 0)

2NO

Time-delay (Stop Cat 1)

3NO

Monitor Contacts

4NO (PNP)

Output Contact 

Ratings

Safety 

Circuit

AC15

C300 (230V AC / Ie=0.75A)

DC13

24V DC / Ie=1A

Time-

delay 

Circuit

AC15

C300 (230V AC/ Ie=0.75A)

DC13

24V DC / Ie=1A

Preset Time

0, 0.5, 1, 2, 4, 6, 8, 10, 15, 20, 25, 30 sec.

Auxiliary Circuit

24V DC / 20 mA (PNP)

Mechanical Durability

10,000,000 operations

Electrical Life

See Output Contact Electrical Life graph (last page)

Rated Current

Total output: 8A max.  1 output 4A max.

Wire Size

HR1S-ATE5110

Single wire: 0.2 to  2.5 mm2 max. (24~14 AWG)

Multiple wires: 0.14 to 0.75 mm2 max.  

HR1S-ATE5110P

Single wire: 0.2 to  2.5 mm2 max.(24~14 AWG)

Multiple wires: 0.2 to 1.5 mm2 max.  

Weight (approx.)

280g

Note:  Safety output contact 

Stop category 0 

 

Time-delay output contact 

Stop category 1

Use a 4A fuse (Type gG) for power protection. Use a 6A fuse (Type gG) for safety output 

• 

protection. Use a 4A fuse (Type gG) for time-delay output and auxiliary output protection.

HR1S-ATE5110 Integrated Terminal Type

HR1S-ATE5110P Removable Terminal Type

EN ISO 13849-1 Performance Level e, Safety Category 4  

 

compliant, and EN 62061 Safety Integrity Level 3.
Integrated and removable teminal styles available.

 

Compact design: 45 mm in width.

 

Time delay outputs: 3NO

 

Auxiliary outputs enable monitoring of power, safety inputs, and a time 

 

delay output
Environmentally friendly, RoHs directive compliant.

 

UL Listed, CSA certified, TÜV NORD approved.                                                                                                                             

 

A1/A2

Fuse

Input A

S12

Input B

S22
Stop 1 

A1/A2 Fuse:  Turns on when power circuit is normal.

 

Input A S12:  Turns on when S11–S12 is closed.

 

Input B S22:  Turns on when S21–S22 is closed.

 

Stop1: 

Turns on when the time-delay output    

 

  

circuits 57-58, 67-68, and 77-78 are closed.

Safety Control Relay HR1S-ATE