manualshive.com logo in svg
background image

Page  14 

7.0  AUXILIARY POWER MODULE 

The Auxiliary Power Module or APM (Cat No. 
PRTAAPM),  illustrated in Fig. 

7, 

is an encapsulated 

power supply that requires a 

120 

Vac input at either 

5 0  

or 

60  Hz.  It provides an output of 32 Vdc (nominal 40  Vdc 
open circuit) which can be used for testing a Digitrip RMS 

5 10 

Trip  Unit. 

When a drawout circuit breaker is equipped with a Dig­
itrip RMS 

5 10 

Trip  Unit,  it can be conveniently set and 

tested while the circuit breaker is out of its cell or in its 
cell in the "Test",  "Disconnect" or "Withdrawn" positions 
by using the Auxiliary Power Module. 

The Auxiliary Power Module is equipped with a unique 
plug-in connector suitable only for plugging into the 
keyed receptacle in the upper right corner of a Digitrip 
RMS Trip  Unit as shown in Fig. 

1. 

This prohibits the pos­

sible use of an incorrect type power module. 

8.0  FRAME RATINGS,  (WHERE APPLICABLE, 

SENSOR RATINGS) AND RATING  PLUGS 

The 

Frame Rating 

of a circuit breaker is the maximum 

RMS current it can carry continuously. The maximum 
Short-Circuit Current Rating of the Circuit breaker are 
usually related to the Frame Rating as well. 

It is often times desirable to be able to choose a current 

value (In),  less than the full frame rating,  to be the basis 
for the coordination of the circuit breaker's  protection 
functions,  without affecting its short-circuit current capa­
bility. For the Digitrip 

5 10 

trip unit this is implemented by 

changing the 

Rating Plug 

(and/or 

Current Sensors, 

where applicable - See your circuit breaker instructions 

(listed in Section 9.0 below) to determine if this applies to 

your circuit breaker). 

The 

(Current) Sensor Rating 

(where applicable) is the 

maximum RMS current the circuit breaker can carry with 
the specified current sensors installed. The Sensor Rat­
ing can be the same or less than the Frame Rating,  but 
not greater. 

The 

Rating Plug 

(See Fig. 6) fits into a special cavity to 

complete the trip unit (See Fig. 

1). 

Rating plugs have two 

current ratings listed on their covers (See Fig. 6): 

1) 

the "Must be used with Frame Rated" cur­
rent value (or "Sensor Rated",  if applica-

I.L.  29-8858 

ble), 

and 2) 

"In 

(Rated I) 

=" 

current value. 

This latter value,  (In)  is the basis for the trip unit current 
settings: 

1) 

2) 

The  Instantaneous and Ground Current 
Settings (if provided)  are multiples of  (In) 

(See Sections 4.6 and 4.8) 

The Long Delay Current Setting, 

Ir , 

is a 

multiple of (In). Long Delay Current Setting 

Ir 

LD x (In). (See Section 4.2) 

3) 

The Short Delay Current Setting (if pro­
vided)  is indirectly dependent upon (In), 
because it is a multiple of 

Ir, 

which in turn 

is a multiple of (In). 

Short Delay Current Setting 

SD x 

Ir 

SD x LD x (In). 

(See Section 4.4) 

Rating Plugs for the Digitrip RMS 

5 10 

trip units are 

marked for and may be applied on both 

5 0  

and 60  Hz 

systems. 

CAUTION 

BEFORE YOU FIT THE RA TING PLUG INTO THE TRIP 
UNIT, 

BE SURE TO 

CHECK 

THAT THE 

BREAKER 

TYPE 

AND 

FRAME RA TlNG 

(OR 

SENSOR RA TING 

IF 

APPLICABLE), 

MA TCH 

THOSE PRINTED ON THE 

RA TlNG PLUG 

COVER. 

INSTALLING A RA TlNG 

PLUG THA T DOES NOT MATCH THE BREAKER 
TYPE AND FRAME RA TlNG (OR SENSOR RA TlNG, IF 

APPLICABLE),  CAN PRODUCE SERIOUS MISCOOR­

DINATION ANDIOR FAILURE OF THE PROTECTION 
SYSTEM. 

Complete catalog descriptions of all available rating 
plugs are given in the applicable circuit breaker supple­

mentary instruction leaflets.  (See Section 

9) 

Note:  Rating plugs from Digitrip models 500/600/7001 
800 CAN NOT be used with model 51 0  trip units. The 
connection pins are located in different positions, so 
that one cannot aCCidentally use the incorrect kind of 
plug. 

Effective May  1997 

www 

. ElectricalPartManuals 

. com

Содержание Digitrip RMS 510 LI

Страница 1: ...IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCE...

Страница 2: ...S Digitrip Type LI LS and LSI trip units can be applied on 3 pole or 4 pole circuit breakers for protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PRO TECTION Re...

Страница 3: ...rotection U Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection UG w w w E...

Страница 4: ...me Instantaneous Ground Protection LS G The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 I...

Страница 5: ...through the circuit breaker exceeds approximately 10 of the frame current sensor rating the green LED will flash On and Off once each second to indicate the trip unit is energized and operating prope...

Страница 6: ...tream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 885...

Страница 7: ...the breaker to trip in a time progressively earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 1 0 minutes it has reset fully so...

Страница 8: ...ght 8 times Ir the Long Delay Setting For currents greater than 8 times Ir the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Set...

Страница 9: ...60 200 240 300 400 UJ 0 600 150 180 210 240 300 360 450 600 UJ a 630 158 189 221 252 315 378 473 630 2 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 400 500 600 750 1000 J 1200 300 360 420 48...

Страница 10: ...it Required following all automatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip...

Страница 11: ...0 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indi cating that there is enough cu...

Страница 12: ...g make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting fr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current excee...

Страница 13: ...attery should be the same type or equivalent Acceptable 3 0 volt lithium batteries may be Fig 6 Typical Rating Plug Trip Unit Connector F u InII Keyed Cavity Page 13 obtained from the following compan...

Страница 14: ...t breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity t...

Страница 15: ...er APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used Fault 3 The br...

Страница 16: ...D any Zone Interlock Wiring The maximum distance between first and last zone is 250 feet 1 1 0 m A Maximum of 20 breakers may be con nected in parallel in one Zone F22 C SO SI 0 1 Sec Legend C Common...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 20: ...SE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer...

Отзывы: