Page 16
I
3200 A
)
..
c:
1
�
'"
�
2
0
N
..,
CD
c:
0
N
3
Main
0.5 Sec
1200 A
Feeder
0.3 Sec
400A
Branch
0.1 Sec
100A
c
Z3
Fig. A. 1 Typical Zone Interlocking (Ground Fault Pro-
Fll
C
SO
SI
0.1 Sec
Ml
C
SO
SI
0.5 Sec
M2
C
SO
SI
0.5 Sec
SI
lN4004
F12
01
0.3 Sec
F21
C
C
SO
SO
SI
SI
0.1 Sec
0.1 Sec
I.L. 29-8858
tection)
Wiring to be twisted pair of AWG No. 1 4
to AWG No. 20.
Route Zone Interlocking wiring sepa
rate from power conductors.
DO NOT GROUND any Zone Interlock
Wiring.
The maximum distance between first
and last zone is 250 feet (1 1 0 m).
A Maximum of 20 breakers may be con
nected in parallel in one Zone.
F22
C
SO
SI
0.1 Sec
Legend
C
=Common
(Ungrounded)
50 =
Short Delay
Output
Signal
to Hi
g
h
e
r
Level Zone
5 I
=
Short Delay
I
nput Signal
from Lower Level Zone
GO
=
Ground
Output
Signal
to
Higher Level Zone
GI
=
Ground
Input Signal
from
Lower Level Zone
/cault at Location
2
2
F23
C
SO
SI
0.1 Sec
Fig. A.2 Typical Zone Interlocking Connections with Two Main Breakers (M1, M2) and a Tie Breaker (T) (Short Delay
Protection)
• !Y·N
Effective May 1997
www
. ElectricalPartManuals
. com
Содержание Digitrip RMS 510 LI
Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...