LOT will reset itself. You can of course,  manually 

clear the LOT (or any other trip indication) at any 
time,  by pushing the "PUSH to RESET" button. 
(See Figure 1 .) 

4.4 Short Delay Current Setting 

There are eight  (8)  available Short Delay Current Set­
tings,  as illustrated in Fig. 4.3. Six settings are in the 
range from 2 to 6 times Ir and the other two settings are 
"S1" or "S2" times Ir'  (REMEMBER:  Ir is the Long Delay 
Current Setting). The values that "S1" and "S2" have 
depend upon the type of circuit breaker,  and are speci­
fied both on the rating plug label (see Fig. 6),  and on the 
applicable Time-Current Curves referenced in 
Section 9.0. 

4.5 Short Delay Time Setting 

As illustrated in Fig. 4.4,  there are two different Short 
Delay curve shapes,  i.e.,  fixed time (flat) or  12t response. 
The shape selected depends on the type of selective 
coordination chosen. The  12t response will provide a 
longer time delay in the low-end of the short delay current 
range than will the flat response. 

Short  Delay 

i"':". .... 

Available  Settings 

2,2.5,3,4, 

5, 6, 

S,.  S2 

Setting 

.. 

m)( 

I, 

In 

Multiples 

of 

��'jg Delay Setting 

,--L 

___ 

__ 

S1  and  S2  Values  are  Specified 

on 

Rating  Plug 

Fig. 4.3  Short Delay Current Settings 

Five flat (.1,  .2,  .3,  .4,  .5 sec.)  and three  12t (.1*,  .3*,  .5* 
sec.) response time delay settings are available. The  12t 
response settings are identified by the suffix asterisk (*) 
that appears in the viewing window. The  12t response is 
applicable to currents  less than eight  (8)  times Ir,  the 
Long Delay Setting.  For currents  greater than 8  times Ir, 

the  12t response reverts to the flat response. 

Note:  See also Section 3.6, Zone Interlocking,  above. 

4.6 Instantaneous Current Setting 

There are eight  (8)  available  Instantaneous Current Set­
tings,  as illustrated in Fig. 4.5. Six settings are in the 

I.L.  29-8858 

range from 2 to 6 times (In) the rating plug value,  and the 
other two settings are "M1" or "M2" times (In). The values 
that "M1" and "M2" have depend upon the type of circuit 
breaker,  and are specified both on the rating plug label 

(see Fig. 6),  and on the applicable Time-Current Curves 

referenced in Section 9.0. 

4.7 NO Instantaneous Current Setting 

For types 

LS 

and 

LSG 

trip units,  please see Sections 3.4 

DIScriminator  (Making Current Release)  and 3.5 OVER­
RIDE (Fixed  Instantaneous),  for available fast-acting high 

short-circuit protection. 

4.8  Ground Fault Current Setting 

The eight  (8)  Ground Fault Current Settings are labeled 
with the code letters "A" through "K" (except there are no 
"G" or "I" settings),  as illustrated in Fig. 4.6.  In general, 
the specific current settings range from 0.25 to 1.0  times 

(In), the rating plug value,  but cannot exceed 1200 A. The 

specific Ground Current Settings for each letter are listed 
in Table 1 and on the applicable Time-Current curve for 
the breaker. 

Sho.'  Delay 

TIme 

[&

Soc. 

;: 

"·"In  Viewing 

Window 

,..... 

Indicates 

I  I 

12t 

Shape 

L.,) 

8  x  I, 

Fig. 4.4  Short Delay Time Settings 

Availab.  '  Settings 

----

.1,  .2,  .3, 

.• . .  

Secondsw.  h 

Flat 

Respom 

12t 

Shape 

Returns 

to 

Flat 

Response 

at Cu 

rn 

lts 

Higher 

than 

x  I, 

Seconds  with 
12t 

Shape 

Effective May  1997 

www 

. ElectricalPartManuals 

. com

Содержание Digitrip RMS 510 LI

Страница 1: ...IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIP MENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK AND ALWAYS FOLLOW GENERALLY ACCE...

Страница 2: ...S Digitrip Type LI LS and LSI trip units can be applied on 3 pole or 4 pole circuit breakers for protection of the neutral circuit IF the circuit breaker is wired and MARKED for NEUTRAL PRO TECTION Re...

Страница 3: ...rotection U Fig 2 2 Long Time Short Time Protection LS Effective May 1997 Fig 2 3 Long Time Short Time Instantaneous Protection LSI Page 3 Fig 2 4 Long Time Instantaneous Ground Protection UG w w w E...

Страница 4: ...me Instantaneous Ground Protection LS G The Digitrip RMS 510 Trip unit provides three basic func tions Protection Information and Testing A typical trip unit and rating plug are illustrated in Fig 1 I...

Страница 5: ...through the circuit breaker exceeds approximately 10 of the frame current sensor rating the green LED will flash On and Off once each second to indicate the trip unit is energized and operating prope...

Страница 6: ...tream breaker s trip unit to the input terminals of the upstream breaker s trip unit For specific instructions see the applicable connection dia grams for your breaker listed in Section 9 0 I L 29 885...

Страница 7: ...the breaker to trip in a time progressively earlier than the Long Delay Time Setting When the load current returns to normal the LTM begins to reset and after about 1 0 minutes it has reset fully so...

Страница 8: ...ght 8 times Ir the Long Delay Setting For currents greater than 8 times Ir the 12t response reverts to the flat response Note See also Section 3 6 Zone Interlocking above 4 6 Instantaneous Current Set...

Страница 9: ...60 200 240 300 400 UJ 0 600 150 180 210 240 300 360 450 600 UJ a 630 158 189 221 252 315 378 473 630 2 800 200 240 280 320 400 480 600 800 9 1000 250 300 350 400 500 600 750 1000 J 1200 300 360 420 48...

Страница 10: ...it Required following all automatic trip and test operations Push then release Test button to test Test operation begins with release of pushbutton Fig 5 Integral Test Panel Lower Right Corner of Trip...

Страница 11: ...0 of the breaker frame or current sensor rating be sure the GREEN Unit Status LED in the lower right corner of the trip unit See Figs 1 and 5 is blinking on and off indi cating that there is enough cu...

Страница 12: ...g make sure the circuit breaker is carrying no more than 50 of the Long Delay Current Setting fr The I L 29 8858 trip unit will not execute your instructions to Test itself when the load current excee...

Страница 13: ...attery should be the same type or equivalent Acceptable 3 0 volt lithium batteries may be Fig 6 Typical Rating Plug Trip Unit Connector F u InII Keyed Cavity Page 13 obtained from the following compan...

Страница 14: ...t breaker can carry with the specified current sensors installed The Sensor Rat ing can be the same or less than the Frame Rating but not greater The Rating Plug See Fig 6 fits into a special cavity t...

Страница 15: ...er APPENDIX A ZONE INTERLOCKING Assume a ground fault of 2000 Amperes occurs and refer to Fig A 1 CASE 1 There is no Zone Selective Interlocking standard time delay coordination is used Fault 3 The br...

Страница 16: ...D any Zone Interlock Wiring The maximum distance between first and last zone is 250 feet 1 1 0 m A Maximum of 20 breakers may be con nected in parallel in one Zone F22 C SO SI 0 1 Sec Legend C Common...

Страница 17: ...I L 29 8858 Page 17 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 18: ...Page 18 I L 29 8858 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 19: ...I L 29 8858 Page 19 NOTES Effective May 1997 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 20: ...SE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Cutler Hammer...

Отзывы: