- 1 -

PK-3P

 110 V

Electromagnetic 

relay

Electromagnetic relay in single-module housing for direct moun-

ting on TH-35 rail.

Applying the supply voltage to the relay coil will switch the con-

tacts to positions 5-6, 8-9 and 11-12. This state is indicated by a 

green LED. After a power failure, the contacts return to positions 

5-4, 8-7 and 11-10.

1. Switch off the power supply.

2. Mount the relay on the rail in the distribution box.

3. Connect the power supply to terminals 1-3. For AC voltage: in 

any order, for DC voltage 1(+) and 3(−).

4. Connect the power supply circuit of the controlled receiver via 

contacts 5-6, 8-9 and 11-12 (NO contacts).

Purpose

Functioning

Assembly

F&F Filipowski sp. j.

Konstantynowska 79/81, 95-200 Pabianice, POLAND

phone/fax (+48 42) 215 23 83 / (+48 42) 227 09 71

www.fif.com.pl; e-mail: [email protected]

Do not dispose of this device in the trash along with other waste!  

According 

to the Law on Waste, electro coming from households free of charge and 

can  give  any  amount  to  up  to  that  end  point  of  collection,  as  well  as  to  sto

-

re the occasion of the purchase of new equipment (in accordance with the 

principle of old-for-new, regardless of brand). Electro thrown in the trash or 

abandoned in nature, pose a threat to the environment and human health.

Summary of Contents for 5908312592389

Page 1: ...onnect the power supply circuit of the controlled receiver via contacts 5 6 8 9 and 11 12 NO contacts Purpose Functioning Assembly F F Filipowski sp j Konstantynowska 79 81 95 200 Pabianice POLAND phone fax 48 42 215 23 83 48 42 227 09 71 www fif com pl e mail biuro fif com pl Do not dispose of this device in the trash along with other waste According to the Law on Waste electro coming from househ...

Page 2: ...ak contact passive 5 COM common contact 6 NO closing contact active 7 NC break contact passive 8 COM common contact 9 NO closing contact active 10 NC break contact passive 11 COM common contact 12 NO closing contact active Connecting diagram ...

Page 3: ...e resistance 3 kV current consumption 25 mA activation time 40 ms deactivation time 20 ms mechanical durability min 5 10 cycles electrical durability min 1 10 cycles power indicator LED power consumption 25 mA working temperature 25 50 C terminal screw terminals 2 5 mm tightening torque 0 4 Nm dimensions 1 module 18 mm mounting on TH 35 rail protection level IP20 modular contactors are recommended...

Page 4: ...e device is in conformity with the essential requirements of The Low Voltage Directive LVD 2014 35 EU and the Electromagnetic Compatibility EMC Directive 2014 30 UE The CE Declaration of Conformity along with the references to the standards in relation to which confor mity is declared can be found at www fif com pl on the product page www fif com pl from the product subpage Warranty CE declaration...

Reviews: